Plan Review Notes For Permit 08080446 |
Permit Number |
08080446 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-26 10:12:45 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- THERE ARE TWO DIFFERENTDESIGN PRESSURES | | CALCULATIONSSUBMITTEDBY TWO DIFFERENT ENGINEERS. | | PROVIDE TWO COPIES OF ENGINEERING CALCULATIONS FROM ONE | | ENGINEER ONLY. | | NOTE: ENGINEERCALCULATIONS ARE NOT REQUIRED. | | CONTRACTORMAY USE TABLE R301.2(2) OF 2004 FLORIDA | | RESIDENTIALCODE TO OBTAIN THE DESIGN PRESSURES. | | | | 2- PROVIDE A COMPLETE INSTALLATION SCHEDULE AS REQUIRED | | BYTHE CITY IMPLEMENTATION STANDARD FOR WIND-BORNE | | DEBRIS IMPACT PROTECTION.SEE ATTACHED SAMPLE. | | ***NOTE:WHEN FILLING UPTHE INSTALLATION SCHEDULE | | MAKE SURE CORRECT ANCHOR SCHEDULE IS REFERENCED.FOR | | EXAMPLE, CONCRETE ANCHOR SCHEDULE MAY NOT BE USED FOR | | CONCRETE BLOCK CONSTRUCTION UNLESS PROPER TESTING IS | | PROVIDED SHOWING THATTHE SUBSTRATETORECEIVE THE | | ACCORDIONSHUTTERS IS POURED CONCRETE WITH MIN. 3,100 | | PSI STRENGTH. | | | | JULIO GOMEZ | | BUILDING PLAN EXAMINER | | (561)805-6712 |
|