Plan Review Notes For Permit 08080403 |
Permit Number |
08080403 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-12-30 15:16:22 | *****UNSAT***** | | | | | | 1. THE TITLE BLOCK INFORMATION LISTED ON THE SUBMITTED | | REVISED SHEETS DOES NOT CORRESPONDS WITH THAT OF THE | | ORIGINALLY APPROVED PLAN SHEETS. FOR EXAMPLE: A) | | REVISED SHEET FA 0.1 WHICH IS THE FIRE ALARM DETAIL | | PLAN READS FIRE ALARM 2ND FLOOR PLAN, B) THE FIRE ALARM | | 2ND FLOOR PLAN SHOULD BE LISTED AS FA 2.0 NOT AS THE | | SECOND (OF 2) FA 1.0 SHEET. | | | | 2. AS PER THIS LOCAL JURISDICTION, DUCT SMOKE DETECTORS | | SHALL INITIATE A GENERAL FIRE ALARM. ON SHEET FA 0.1, | | AMEND FIRE ALARM SYSTEM INPUT #10 TO REFLECT THIS | | REQUIREMENT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|