Plan Review Notes
Plan Review Notes For Permit 08080403
Permit Number 08080403
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-12-30 15:16:22*****UNSAT*****
  
  
 1. THE TITLE BLOCK INFORMATION LISTED ON THE SUBMITTED
 REVISED SHEETS DOES NOT CORRESPONDS WITH THAT OF THE
 ORIGINALLY APPROVED PLAN SHEETS. FOR EXAMPLE: A)
 REVISED SHEET FA 0.1 WHICH IS THE FIRE ALARM DETAIL
 PLAN READS FIRE ALARM 2ND FLOOR PLAN, B) THE FIRE ALARM
 2ND FLOOR PLAN SHOULD BE LISTED AS FA 2.0 NOT AS THE
 SECOND (OF 2) FA 1.0 SHEET.
  
 2. AS PER THIS LOCAL JURISDICTION, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM. ON SHEET FA 0.1,
 AMEND FIRE ALARM SYSTEM INPUT #10 TO REFLECT THIS
 REQUIREMENT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW