2008-10-06 11:36:20 | PLUMBING PLAN REVIEW: |
| DENIED **2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| **THE FOLLOWING COMMETS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. SHEET 2, REVISED PLUMBING RISER: PLEASE CORRECT THE |
| FOLLOWING ITEMS PER THE FBC-2004 PLUMBING CODE |
| SECTIONS. |
| |
| A} THE SHOWER AND TUB REQUIRE A VENT. PER SECTION |
| 901.2.1 VENTING REQUIRED. |
| |
| **NO COMMENT RESPONSE FROM THE DESIGNER, AND THE |
| RESUBMITTED PLUMBING RISER WITH THE REVISED VENTING FOR |
| THE TUB AND SHOWER IS NOT COMPLIANT. THE RESUBMITTED |
| RISER DIAGRAM IS INDICATING A HORIZONTAL DRY VENT FOR |
| THE TUB AND SHOWER. PLEASE KNOW THAT EVERY DRY VENT |
| CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE |
| THE CENTERLINE OF THE HORIZONTAL DRAIN. PLEASE |
| REFERENCE THE RED LINE CORRECTIONS INDICATING COMPLIANT |
| VENTING FOR THE TUB AND SHOWER. PER FBC-2004 PLUMBING |
| SECTION 905.3 VENT CONNECTIONS TO DRAINAGE. |
| |
| B} **"OK", COMMENT ADDRESSED. |
| |
| C} **"OK", COMMENT ADDRESSED. |
| |
| D} **"OK", COMMENT ADDRESSED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |