Plan Review Notes For Permit 08080400 |
Permit Number |
08080400 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-10-06 10:20:53 | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | THESE ARE REPEAT COMMENTS FROM THE PREVIOUS REVIEW | | | | 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED***LOCATE | | ON THE PLANS OR | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | PER 210.11(C) (3, NOTE SAME ON PLANS FOR THE REMODELED | | BATH. | | | | NOTE: AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF | | WORK | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|