Plan Review Notes
Plan Review Notes For Permit 08080400
Permit Number 08080400
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-05 10:31:532004 FBC W/2007 REVISIONS
 ADDITION AND LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 317
  
 2) SPECIFY THE ROOF OVERHANG ON THE PLANS. FBC 13-600
  
 3) SHOW COMPLIANCE WITH FBC R806.2 ATTIC VENTILATION
 FOR THE ADDITION. SPECIFY THE SIZE AND LOCATION OF
 VENTS.
  
 4) THE TYPICAL WALL AND BEAM ATTACHMENT DETAIL ON SHEET
 2 SPECIFIES 4 #5 DOWELS IN THE 12" OPEN COLUMN. THE
 PLANS SPECIFY 2 #5 BARS AT THIS LOCATION EVERYWHERE
 ELSE. PLEASE CORRECT.
  
 5) THE PRESCRIPTIVE METHOD ON ENERGY CODE FORM 600C-04R
 REQUIRES CONCRETE BLOCK WALLS TO HAVE A MINIMUM OF R-5
 INSULATION. PLEASE CORRECT.
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) THE PROPERTY IS LOCATED IN AN AREA OF QUESTIONABLE
 SOIL. SUBMIT 2 COPIES OF A GEO-TECHNICAL EVALUATION
 SOILS REPORT. FBC R401.4 THE SOIL DENSITY TEST REPORTS
 THAT WERE SUBMITTED ARE NOT ADEQUATE.
  
 8) ALL CHANGES TO THE PLANS ARE REQUIRED TO BE MADE BY
 THE DESIGNER OF RECORD (ARCHITECT). FS481
  