2008-09-05 10:31:53 | 2004 FBC W/2007 REVISIONS | | ADDITION AND LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. FS 317 | | | | 2) SPECIFY THE ROOF OVERHANG ON THE PLANS. FBC 13-600 | | | | 3) SHOW COMPLIANCE WITH FBC R806.2 ATTIC VENTILATION | | FOR THE ADDITION. SPECIFY THE SIZE AND LOCATION OF | | VENTS. | | | | 4) THE TYPICAL WALL AND BEAM ATTACHMENT DETAIL ON SHEET | | 2 SPECIFIES 4 #5 DOWELS IN THE 12" OPEN COLUMN. THE | | PLANS SPECIFY 2 #5 BARS AT THIS LOCATION EVERYWHERE | | ELSE. PLEASE CORRECT. | | | | 5) THE PRESCRIPTIVE METHOD ON ENERGY CODE FORM 600C-04R | | REQUIRES CONCRETE BLOCK WALLS TO HAVE A MINIMUM OF R-5 | | INSULATION. PLEASE CORRECT. | | | | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | 7) THE PROPERTY IS LOCATED IN AN AREA OF QUESTIONABLE | | SOIL. SUBMIT 2 COPIES OF A GEO-TECHNICAL EVALUATION | | SOILS REPORT. FBC R401.4 THE SOIL DENSITY TEST REPORTS | | THAT WERE SUBMITTED ARE NOT ADEQUATE. | | | | 8) ALL CHANGES TO THE PLANS ARE REQUIRED TO BE MADE BY | | THE DESIGNER OF RECORD (ARCHITECT). FS481 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|