2008-09-02 09:51:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PAGE 14. AN EDGE DISTANCE OF 2" REQUIRES A
 FACTOR OF .50.
  
 2. SEE CONNECTION D, 8" REQUIRED FOR 3 1/2" EDGE
 DISTANCE, BUT THIS WAS NOT CIRCLED ON THE PRODUCT
 APPROVAL AND 9" WAS SPECIFIED. PLEASE CHECK THIS
 CONNECTION PRIOR TO RESUBMITTAL AS THE OTHER CONNECTION
 TYPES WERE CONSISTENT WITH THE TABLE, BUT DID NOT HAVE
 THE FACTOR APPLIED. THIS ONE IS NOT COMPLIANT WITH THE
 ANCHOR CHART EVEN IF THE EDGE DISTANCE IS REVISED.
 CHECK ALL.
  
  
  
  
  