2008-09-02 09:51:42 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. SEE PAGE 14. AN EDGE DISTANCE OF 2" REQUIRES A | | FACTOR OF .50. | | | | 2. SEE CONNECTION D, 8" REQUIRED FOR 3 1/2" EDGE | | DISTANCE, BUT THIS WAS NOT CIRCLED ON THE PRODUCT | | APPROVAL AND 9" WAS SPECIFIED. PLEASE CHECK THIS | | CONNECTION PRIOR TO RESUBMITTAL AS THE OTHER CONNECTION | | TYPES WERE CONSISTENT WITH THE TABLE, BUT DID NOT HAVE | | THE FACTOR APPLIED. THIS ONE IS NOT COMPLIANT WITH THE | | ANCHOR CHART EVEN IF THE EDGE DISTANCE IS REVISED. | | CHECK ALL. | | | | | | | | | | |
|