Plan Review Notes For Permit 08080373 |
Permit Number |
08080373 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-10-24 14:20:40 | REVISION #1: ONE BATHROOM TO REMAIN. | | | | ******PROVISO****** | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS | | SHALL BE PROHIBITED. A PLUMBING PERMIT IS REQUIRED AND | | AN INSPECTION IS REQUIRED OF THE PLUMBING DEMO WORK | | PRIOR TO COVERING DEMO WORK WITH FINNISH WALLS, | | CIELINGS, OR POURED CONCRETE SLABS. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|