2008-08-21 14:43:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN A-0 APPLICABLE CODE INFORMATION STATES 'FLORIDA
 STATE CODE 2001' THE PERMIT BEING APPLIED FOR IS UNDER
 THE 2004 FBC WITH 2007 SUPPLEMENTS, PLEASE CORRECT
 PLAN.
  
 2) PLEASE ADD A DETAIL TO THE MECHANICAL PLANS FOR THE
 INSTALLATION OF THE FIRE DAMPERS. PER 2004 FBC/M THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]