2008-09-03 16:22:57BUILDING PLAN REVIEW
 PERMIT: 08080371
 ADD: 250 S. AUSTRALIAN AVE #600
 CONT: FISHER CONTRACTING CORP.
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-0 MAKES REFERENCE TO THE 2001 CODE. PLANS
 SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER JULY
 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC BUILDING
 WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE EXISTING
 FLOOR LAYOUT, AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO THE EXISTING FLOOR PLAN. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE. FBC 106.1.1
  
 6) SHEET FP1.1. ANY PENETRATION THROUGH THE FIRE
 PARTITION SHALL MEET THE REQUIREMENTS OF FBC 712.3.1.2.
 PROVIDE THE UL ASSEMBLY DETAIL AND THE UL NUMBER FOR
 ALL PENETRATIONS (FIRE SPRINKLER PIPES) OF THE NEW FIRE
 WALL: SHOW ALL DETAILS ON THE PLANS.
  
 7) SHEET A-1 MAKES REFERENCE TO DETAIL #2 ON THE SHEET,
 HOWEVER, DETAIL #2 REFERS TO THE FINISH SCHEDULE. ON
 THIS SAME SHEET DOOR TYPE ?B? DOES NOT INDICATE THE
 RATING (HOUR) OF THE DOOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  