2009-03-26 15:46:35 | ** DENIED REVIEW ** |
| |
| *** PLEASE SEE ALL NOTES ISSUED ON PROVISO DATED |
| 12/18/08. MOST OF THESE COMMENTS STILL NEED TO BE |
| ADDRESSED. |
| |
| 1) NOTE: CIRCUITING ON PLANS NEEDS TO COORDINATE WITH |
| ALL PANEL SCHEDULES AND ALL ELECTRICAL ON PLANS NEEDS |
| TO BE CIRCUIT. SOME EXAMPLES WILL BE GIVEN. |
| |
| FOR EXAMPLE: PLEASE SEE LIGHTING FIXTURES IN AREA 931 |
| WHICH DO NOT SHOW ANY CONTROLS OR CIRCUITING. |
| THIS WILL ALSO BE NOTED FOR FBC CHAPTER 13 COMMENTS |
| WITH RESPECT TO MINIMUM LIGHTING CONTROLS REQUIRED. |
| |
| FOR EXAMPLE: PLEASE SEE LIGHTING OUTSIDE 918 AND 919 IN |
| HALLWAY WHICH DO NOT INDICATE ANY CONTROLS OR |
| CIRCUITING. |
| THIS WILL ALSO BE NOTED FOR FBC CHAPTER 13 COMMENTS |
| WITH RESPECT TO MINIMUM LIGHTING CONTROLS REQUIRED. |
| |
| FOR EXAMPLE: PLEASE SEE CIRCUITS L9L29 THIS DOES NOT |
| CORRELATE WITH THE ROOM/AREA DESIGNATION ON PLANS AND |
| PANEL SCHEDULES. ANOTHER WOULD BE L9L14, L9L28, THESE |
| ARE SOME EXAMPLES AND ARE NOT ALL. |
| |
| 408.4. |
| FBC 106.1.2, 106.1.1, 106.5 |
| |
| 2) NOTE: AS NOTED ABOVE WITH RESPECT TO LIGHTING |
| CONTROLS THERE ARE LIGHTING FIXTURES WHICH DO NOT |
| INDICATE LIGHTING CONTROLS MEETING FBC |
| 13-415.1.ABC.1.1, .1.2. |
| PLEASE SEE PREVIOUS NOTES WITH RESPECT TO KEYPADS AND |
| INFORMATION NEEDED. |
| PLEASE PROVIDE. |
| |
| 3) NOTE: PLEASE VERIFY NEW RECEPTACLES FOR |
| COPIERS/PRINTERS. CIRCUITS L9L23, AND L9R15 BOTH APPEAR |
| TO BE FOR COPIERS HOWEVER ONE IS NOTED FOR A PRINTER? |
| THIS DOES NOT ACCURATE. |
| 4108.4, 220, 240.4 ETC. |
| |
| 4) NOTE: PLEASE CORRELATE RISER WITH PANEL SCHEDULES |
| AND PLANS. |
| FOR EXAMPLE: THE RISER INDICATES PANELS 8L AND 8LA, |
| HOWEVER THE PANEL SCHEDULES SUBMITTED ARE FOR L9L, L9R, |
| L9LA. |
| THERE ARE NOT ANY OF THESE PANELS ON RISER. IN FACT |
| WHAT IS L9LA? |
| THE RISER INDICATES A 24CIRCUIT PANEL OF SOME SORT FROM |
| 8L HOWEVER THIS CAN ONLY BE ASSUMED TO BE THE LIGHTING |
| CONTROL PANEL. AS THE PANEL SCHEDULE ONLY STATES SUB |
| PANEL ON L9L IT IS NOT CLEAR. |
| THIS ALSO NOW INCLUDES WORK ON THE 8TH FLOOR WHICH WAS |
| NOT PART OF ORIGINAL PLANS, PANEL SCHEDULES, RISER ETC. |
| PANEL *H* WHICH IS ONLY NOW BEING SUBMITTED FOR THE |
| FIRST TIME TO REVIEW IS SHOWN AS 120/208 YET RISER |
| CLEARLY INDICATES THIS AS 277/480V. |
| NOTE MENTIONS LOADS ON PANELS WERE NOT KNOWN HOWEVER |
| BASED ON THE INITIAL DATE GIVEN ON PROVISO, LOADS MOST |
| CERTAINLY COULD HAVE BEEN RECORDED AND INDICATED. |
| |
| PLEASE COORDINATE ALL PLANS, CIRCUITS, PANELS, RISER AS |
| NOTED ON ORIGINAL PROVISO. |
| 408,215.5, 220,310,ETC GIVEN AS SOME GENERAL CODE |
| SECTIONS. |
| |
| 5) NOTE: PLEASE SEE PREVIOUS PROVISO NOTES FOR |
| COMPLIANCE WIHT FBC 11-4.28.1, .2 AND .3. NOT |
| ADDRESSED. SEE SEPARATE NOTES PRINTED OUT AND ATTACHED |
| FROM PROVISO. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |