Date |
Text |
2008-12-18 16:31:22 | ** PROVISO ** |
| |
| 1) NOTE: PLEASE SUBMIT PLANS WITH REVISED CIRCUITING |
| FOR ALL LIGHTING AND RECEPTACLES. SOME NEW RECEPTACLES |
| ARE STILL SHOWN WITH OUT ANY CIRCUITS? |
| PLEASE BE SURE TO SUBMIT A REVISED PANEL SCHEDULE FOR |
| THE 277/480V LIGHTING PANEL WHICH IS NOT SUBMITTED OR |
| SHOWN. |
| *** NEW CIRCUITS SHALL BE IDENTIFIED. 408.4 SCHEDULE ON |
| SITE SHALL ALSO IDENTIFY ALL EXISTING. |
| ALL SHALL BE REVISED. VERIFY 30 CIRCUIT 225AMP PANELS |
| AS SHOWN ON SCHEDULES AND RISER. |
| |
| 2) NOTE: PLEASE SUBMIT A REVISED SHEET 1.1A FOR MINIMUM |
| REQUIRED LEVELS FOR ADA COMPLIANCE. THIS WAS IN |
| PREVIOUS COMMENTS HOWEVER THE SHEET SUBMITTED ONLY |
| QUOTES THE CODE. CD LEVELS WERE REVISED ON ELECTRICAL. |
| FBC 11-4.28.1,.2 AND .3. |
| |
| 3) NOTE: NO NOTES WERE ADDED WITH RESPECT TO KEYPADS |
| MEETING THE EXCEPTIONS OF FBC 13-415.1.ABC.1.1,1.2. THE |
| OCCUPANT MUST SEE ALL LIGHTING WHICH IS BEING |
| CONTROLLED OR MEET EXCEPTIONS. |
| PILOT LIGHTS WITH PERMANENT LABELING OF AREAS AND ROOMS |
| WHICH ARE BEING CONTROLLED ARE REQUIRED. |
| |
| 4) NOTE: LOAD ON TWO COPIERS SHALL BE VERIFIED AS THESE |
| ARE SHOWN ON GENERAL RECEPTACLES CIRCUITS. |
| PREVIOUS PLANS INDICATED TWO NEW DEDICATED CIRCUITS |
| HOWEVER THESE ARE NOW ON GENERAL RECEPTACLE CIRCUITS. |
| 220,408.4,310.16,240.4 |
| |
| ** THE ABOVE SHALL BE SUBMITTED FOR REVIEW AND STAMPING |
| BEFORE FINAL INSPECTION. |
| |
| ** ELECTRICAL PERMIT REQUIRED. |
| ** LOW VOLTAGE WORK AS SHOWN IS REQUIRED TO BE ON A |
| SEPARATE PERMIT FROM ELECTRICAL PERMIT. THESE PLANS MAY |
| BE REFERENCED FOR THIS SCOPE OF WORK AS SHOWN. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |