2008-09-08 10:20:34*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE PRROJECTED SCOPE OF WORK SHALL NOT HINDER OR
 INTEREFERE WITH ACCESS TO AND/OR EGRESS FROM OTHER
 FLOORS OF THE BUILDING.
  
 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4. BASED UPON OCCUPANCY CLASSIFICATION, PLEASE PROVIDE
 THE OCCUPANT LOAD FOR THE PROJECT SITE.
  
 5. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE
 TO EXITS.
  
 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE
 NEW NINTH FLOOR PLAN.
  
 7. SHOW THE LOCATION OF THE FIRE ALARM DEVICES FOR THE
 NEW NINTH FLOOR PLAN.
  
 8. SHOW THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE.
  
 9. SPECIFY THE INTERIOR WALL FINISH MATERIALS IN TERMS
 OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW