Plan Review Notes
Plan Review Notes For Permit 08080340
Permit Number 08080340
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-29 16:07:01 
  
  
  
  
 ** DENIED **
  
  
  
 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS
 NOTED BELOW FOR DESIGN.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLANS NEED TO BE COMPLETED FOR LIGHTING
 CONTROL SYSTEM PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 STATING ON PLANS THAT THE SYSTEM SHALL BE LUTRON SOFT
 TOUCH OR EQUAL DOES NOT PROVIDE ENOUGH INFORMATION FOR
 REVIEW. PLEASE SHOW ALL DEVICES, LOCATIONS, OVER RIDES,
 OVER RIDE TIMES ETC
  
 3) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2
 PLEASE COMPLETE FIXTURE LEGEND ETC. AS THIS IS NOT
 COMPLETE AT THIS TIME THE LIGHTING PERFORMANCE LEVELS
 AS SHOWN CAN NOT BE CONFIRMED TO BE CODE COMPLIANT.
  
 4) NOTE: PLEASE SEE THAT PANEL ON SECONDARY SIDE OF
 TRANSFORMER SHALL MEET 408.36, 240.21, 310.16, 240.4
  
 5) NOTE: PLEASE SEE FEEDERS ON THE SECONDARY SIDE OF
 TRANSFORMER SHALL MEET 240.21, 310.16, 240.4
  
 6) NOTE: PLEASE SEE 408.4, ALL NEW CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. STATING
 *RECEPTACLES* OR *LIGHTING* IS NOT PERMITTED.
  
 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.2.1, .2.2
  
 8) NOTE: PLEASE COORDINATE PLANS. THE ELECTRICAL
 SERVICE EQUIPMENT SHOWN ON PLANS IS NOT THAT OF THE
 SAME EQUIPMENT SHOWN ON RISER AND PANEL SCHEDULES.
 220,215,408,310,ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF DOCUMENTS.
 FBC 106.3.5.1.2 FOR COMPLETED PLANS.
  
 9) NOTE: PLEASE SHWO AND INDICATE ALL MINIMUM DEVICE
 LOCATIONS AND LEVELS PER FBC 11-4.28.1,.2 AND .3.
 BASE PLANS ARE REQUIRED TO MINIMUM DEISGN FIRE ALARM
 SYSTEM PER FS 633
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  