2008-09-02 10:11:25BUILDING PLAN REVIEW
 PERMIT: 08080340
 ADD: 1645 PALM BEACH LAKES # 900
 CONT: LTI DEVELOPMENT
 TEL: (561)718-6243
  
 SEPT. 02.08
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION919.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
  
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. PLANS SUBMITTED FOR PERMIT (FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
 2004 EXISTING BUILDING CODE/ 2007 SUPPLEMENTS.
 B) LEVEL OF ALTERATION: 2004 EXISTING BUILDING CODE
 301.5 A DESIGN PROFESSIONAL MUST ELECT ONE LEVEL OF
 ALTERATION PURSUANT TO SECTION 303,304 & 305.
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 D) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 3) SHEET 1.0A INDICATE A NEW BREAK ROOM BUT THERE IS NO
 INFORMATION ON THE BREAK ROOM CABINETS COUNTER AND
 SINK. PLEASE PROVIDE COMPLIANCE WITH: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4
  
 4) SHEET 1.0A INDICATES A NEW BREAK ROOM WITH NEW WASTE
 LINES BUT NO PLUMBING DETAILS NOR FIRE PROOFING DETAILS
 WHERE THE WASTE WILL PENETRATE THE FIRE RATED FLOOR
 ASSEMBLY. 712.4.1.
  
 5) SHEET 2.0E THE RIGHT SET OF STAIRS IS MISSING THE
 EXIT LIGHT AT THE ENTRY OF THE VERTICAL EXIT. TABLE
 1006.
  
 6) PLANS DO NOT INDICATE THAT NO COMBUSTIBLE MATERIALS
 CAN BE USED IN THE CONSTRUCTION OF WALL FRAMING. TABLE
 601, AND SECTION 603.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.