2008-08-20 11:34:05DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. MANUF. SPECIFICATION SHEETS FOR THE DRYERS DOES NOT
 INDICATE A LISTING FROM AN APPROVED TESTING AGENCY.
 SECTION 301.3.
  
 2. THE WELDING CERTIFICATIONS SHALL BE SUBMITTED WITH A
 PHOTO IDENTIFICATION OF THE WELDER PER AWS
 CERTIFICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  