Plan Review Notes
Plan Review Notes For Permit 08080310
Permit Number 08080310
Review Stop B
Sequence Number 2
Notes
Date Text
2008-08-25 16:20:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.CONCRETE BLOCK SUBSTRATE SPECIFIED ON THE
 INSTALLATION SCHEDULE.MOUNTING TYPE I REQURES A
 CONCRETE SUBSTRATE.
  
 THIS WAS REVISED FOR CONNECTION TYPE "A", BUT NOT "I".
 SEE PAGE 15 OF PRODUCT APPROVAL. PLEASE CHECK ALL.
 FBC16.
  
 2. THE FIRST TWO PAGES OF A MIAMIDADE NOA WAS SUBMITTED
 AS WELL AS THE FLOIRIDA STATE PRODUCT APPROVAL.THE
 SHUTTER GLASS SEPARATION SPECIFIED ON THE INSTALLATION
 SCHEDULE IS NOT COMPLIANT FOR THE NOA.PLEASE EITHER
 REVISE THE INSTALLATION SCHEDULE AND SUBMIT THE
 COMPLETE NOA, OR REMOVE THE NOA FROM THE PACKAGE.YOU
 CANNOT SUBMIT THIS TO BE A PART OF THE PERMIT PACKAGE
 IF YOU DO NOT WISH TO COMPLY WITH THE INSTALLATION
 REQUIREMENTS OF THE NOA.
  
 3.INFORMATIONAL ONLY - THE INFORMATION HIGHLIGHTED ON
 THE PRODUCT APPROVAL WAS FOR ALL POINTS SOLID SET
 RATHER THAN TAPCONS, SEE THE TOP LEFT CORNER OF PAGE
 13.THIS WOULD HAVE REQUIRED DIFFERENT ANCHOR SPACING,
 BUT AS THE CONTRACTOR HAD USED THE 75PSF COLUMN (RATHER
 THAN 40PSF), THE ANCHOR SPACING ON THE INSTALLATION
 SCHEDULE MEETS THE MINIMUM REQUIRED BY CODE.HOWEVER,
 I AM BRINGING THIS TO YOUR ATTENTION TO AVOID FUTURE
 ISSUES.