2008-08-25 16:20:50 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.CONCRETE BLOCK SUBSTRATE SPECIFIED ON THE |
| INSTALLATION SCHEDULE.MOUNTING TYPE I REQURES A |
| CONCRETE SUBSTRATE. |
| |
| THIS WAS REVISED FOR CONNECTION TYPE "A", BUT NOT "I". |
| SEE PAGE 15 OF PRODUCT APPROVAL. PLEASE CHECK ALL. |
| FBC16. |
| |
| 2. THE FIRST TWO PAGES OF A MIAMIDADE NOA WAS SUBMITTED |
| AS WELL AS THE FLOIRIDA STATE PRODUCT APPROVAL.THE |
| SHUTTER GLASS SEPARATION SPECIFIED ON THE INSTALLATION |
| SCHEDULE IS NOT COMPLIANT FOR THE NOA.PLEASE EITHER |
| REVISE THE INSTALLATION SCHEDULE AND SUBMIT THE |
| COMPLETE NOA, OR REMOVE THE NOA FROM THE PACKAGE.YOU |
| CANNOT SUBMIT THIS TO BE A PART OF THE PERMIT PACKAGE |
| IF YOU DO NOT WISH TO COMPLY WITH THE INSTALLATION |
| REQUIREMENTS OF THE NOA. |
| |
| 3.INFORMATIONAL ONLY - THE INFORMATION HIGHLIGHTED ON |
| THE PRODUCT APPROVAL WAS FOR ALL POINTS SOLID SET |
| RATHER THAN TAPCONS, SEE THE TOP LEFT CORNER OF PAGE |
| 13.THIS WOULD HAVE REQUIRED DIFFERENT ANCHOR SPACING, |
| BUT AS THE CONTRACTOR HAD USED THE 75PSF COLUMN (RATHER |
| THAN 40PSF), THE ANCHOR SPACING ON THE INSTALLATION |
| SCHEDULE MEETS THE MINIMUM REQUIRED BY CODE.HOWEVER, |
| I AM BRINGING THIS TO YOUR ATTENTION TO AVOID FUTURE |
| ISSUES. |