Plan Review Notes
Plan Review Notes For Permit 08080260
Permit Number 08080260
Review Stop E
Sequence Number 3
Notes
Date Text
2008-11-04 16:09:58 
  
 PROVISO
  
 250.32(B)(2) GROUNDED CONDUCTOR WHERE (1) AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT RUN WITH THE SUPPLY TO THE
 BUILDING OR STRUCTURE, (2) THERE ARE NO CONTINUOUS
 METALLIC PATHS BONDED TO THE GROUNDING SYSTEM IN EACH
 BUILDING OR STRUCTURE INVOLVED, AND (3) GROUND-FAULT
 PROTECTION OF EQUIPMENT HAS NOT BEEN INSTALLED ON THE
 SUPPLY SIDE OF THE FEEDER(S), THE GROUNDED CONDUCTOR
 RUN WITH THE SUPPLY TO THE BUILDING OR STRUCTURE SHALL
 BE CONNECTED TO THE BUILDING OR STRUCTURE DISCONNECTING
 MEANS AND TO THE GROUNDING ELECTRODE(S) AND SHALL BE
 USED FOR GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES,
 OR FRAMES REQUIRED TO BE GROUNDED OR BONDED.---IF THESE
 CONDITIONS ARE NOT MET, AN EQUIPMENT GROUND MUST BE
 INSTALLED WITH THE FEEDERS, AND THE NEUTRAL ISOLATED
 INTHE EXISTING MAIN SWITCHGEAR.