Plan Review Notes
Plan Review Notes For Permit 08080260
Permit Number 08080260
Review Stop B
Sequence Number 1
Notes
Date Text
2008-09-09 15:55:032004 FBC W/2007 REVISIONS
 COMMERCIAL GENERATOR
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) SPECIFY THE CODE EDITION AND DESIGN PARAMETERS USED
 TO DETERMINE WIND LOADS. SEE 2004 FBC W/2007 REVISIONS
 SECTION 1609 AND ASCE 7-02.
  
 3) SPECIFY WINDSPEED AND EXPOSURE CATEGORY ON THE
 PLANS. MINIMUM OF 140 MPH, 3 SECOND GUST FOR CITY OF
 WEST PALM BEACH. SEE FBC 1609.
  
 4) SPECIFY WIND DESIGN DATA REQUIRED BY FBC 1603.1.4 ON
 THE PLANS.
  
 5) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE
 FUEL TANK TO THE SLAB AT THE 12- 1" DIAMETER ANCHOR
 HOLES SHOWN ON SHEET SD1. FBC 1609.1.3
  
 6) SPECIFY HOW THE GENERATOR WILL BE ATTACHED TO THE
 FUEL TANK. FBC 1609.1.3
  
 7) EQUIPMENT IS LOCATED IN AN AO FLOOD ZONE. ELEVATION
 OF THE TOP OF THE SLAB IS REQUIRED TO BE VERIFIED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]