Plan Review Notes For Permit 08080260 |
Permit Number |
08080260 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-09-09 15:55:03 | 2004 FBC W/2007 REVISIONS | | COMMERCIAL GENERATOR | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. FS 713 | | | | 2) SPECIFY THE CODE EDITION AND DESIGN PARAMETERS USED | | TO DETERMINE WIND LOADS. SEE 2004 FBC W/2007 REVISIONS | | SECTION 1609 AND ASCE 7-02. | | | | 3) SPECIFY WINDSPEED AND EXPOSURE CATEGORY ON THE | | PLANS. MINIMUM OF 140 MPH, 3 SECOND GUST FOR CITY OF | | WEST PALM BEACH. SEE FBC 1609. | | | | 4) SPECIFY WIND DESIGN DATA REQUIRED BY FBC 1603.1.4 ON | | THE PLANS. | | | | 5) SPECIFY THE ANCHORS THAT WILL BE USED TO ATTACH THE | | FUEL TANK TO THE SLAB AT THE 12- 1" DIAMETER ANCHOR | | HOLES SHOWN ON SHEET SD1. FBC 1609.1.3 | | | | 6) SPECIFY HOW THE GENERATOR WILL BE ATTACHED TO THE | | FUEL TANK. FBC 1609.1.3 | | | | 7) EQUIPMENT IS LOCATED IN AN AO FLOOD ZONE. ELEVATION | | OF THE TOP OF THE SLAB IS REQUIRED TO BE VERIFIED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|