Plan Review Notes
Plan Review Notes For Permit 08080212
Permit Number 08080212
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-13 16:58:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1 SANITARY ISOMETRIC AND PLUMBING FLOOR
 PLAN: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004
 PLUMBING CODE SECTIONS.
  
 A} THE WASHING MACHINE MUST DRAIN DOWN STREAM OF THE
 NEW MATER BATH WET VET. ONLY FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT. PER SECTION 909.1
 WET VENT PERMITTED.
  
 B} CLEARLY INDICATE THE SIZE TO ALL FIXTURE TRAPS
 (WASHING MACHINE MINIMUM 2" AND LAVATORY MINIMUM 1-1/4"
 TRAPS ARE NOT SIZED). PER SECTION 701.1 SCOPE.
  
 C} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER AS BEING A
 TWO-WAY CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN
 AND BUILDING SEWER JUNCTION.
  
 2. SHEET P-1 PLUMBING FLOOR PLAN IS TO LIGHT AND HARD
 TO READ, PLEASE CORRECT. PER (W.P.B. AS AMENDED)
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SHEET P-1 GAS ISOMETRIC: PLEASE KNOW THAT THE
 CORRECT SIZING TABLE IS 402.4(2) NOT 402.4(1) DUE TO
 FLORIDA PUBLIC UTILITIES PROVIDING A 12" WC WITH A .5"
 PRESSURE DROP. PER FBC-2004 FUEL GAS TABLE 402.4(2).
  
 4. PLEASE KNOW THAT ENERGY CALCULATIONS FOR THE NEW
 TANKLESS WATER HEATER AND HOT WATER PIPE INSULATION ARE
 REQUIRED. PER FBC-2004 CHAPTER 13 SECTION 13-612.1.C.1
 ADDITIONS, TABLE 13-612.1.ABC.3.2 MINIMUM PERFORMANCE
 STANDARDS WATER HEATING EQUIPMENT, AND TABLE
 611.1.ABC.1 MINIMUM PIPE INSULATION.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]