2008-08-13 16:58:44 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-1 SANITARY ISOMETRIC AND PLUMBING FLOOR |
| PLAN: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004 |
| PLUMBING CODE SECTIONS. |
| |
| A} THE WASHING MACHINE MUST DRAIN DOWN STREAM OF THE |
| NEW MATER BATH WET VET. ONLY FIXTURES WITHIN THE |
| BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. PER SECTION 909.1 |
| WET VENT PERMITTED. |
| |
| B} CLEARLY INDICATE THE SIZE TO ALL FIXTURE TRAPS |
| (WASHING MACHINE MINIMUM 2" AND LAVATORY MINIMUM 1-1/4" |
| TRAPS ARE NOT SIZED). PER SECTION 701.1 SCOPE. |
| |
| C} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF |
| THE BUILDING DRAIN AND BUILDING SEWER AS BEING A |
| TWO-WAY CLEANOUT. PER SECTION 708.3.5 BUILDING DRAIN |
| AND BUILDING SEWER JUNCTION. |
| |
| 2. SHEET P-1 PLUMBING FLOOR PLAN IS TO LIGHT AND HARD |
| TO READ, PLEASE CORRECT. PER (W.P.B. AS AMENDED) |
| SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. SHEET P-1 GAS ISOMETRIC: PLEASE KNOW THAT THE |
| CORRECT SIZING TABLE IS 402.4(2) NOT 402.4(1) DUE TO |
| FLORIDA PUBLIC UTILITIES PROVIDING A 12" WC WITH A .5" |
| PRESSURE DROP. PER FBC-2004 FUEL GAS TABLE 402.4(2). |
| |
| 4. PLEASE KNOW THAT ENERGY CALCULATIONS FOR THE NEW |
| TANKLESS WATER HEATER AND HOT WATER PIPE INSULATION ARE |
| REQUIRED. PER FBC-2004 CHAPTER 13 SECTION 13-612.1.C.1 |
| ADDITIONS, TABLE 13-612.1.ABC.3.2 MINIMUM PERFORMANCE |
| STANDARDS WATER HEATING EQUIPMENT, AND TABLE |
| 611.1.ABC.1 MINIMUM PIPE INSULATION. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |