2008-08-14 11:55:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE MECHANICAL PLAN PAGE M-1. PLEASE MAKE THE FLOOR
 PLAN OF THE HOUSE DARKER AS OUR ELECTRONIC SCANNER FOR
 RECORD RETENTION WILL NOT BE ABLE TO RECORD IT, PER
 2004 W.P.B. AMEND. 106.1.3.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.2. SHORT FORM 600C-04 MAY BE USED AS THE
 ADDITION IS UNDER 600 SQ. FT., SEE 2004 FBC
 13-600.3.C.
  
 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS FOR THE
 ADDITION, IF SUBMITTED FOR THE WHOLE HOUSE PLEASE
 SEPARATE EXISTING HOUSE FROM ADDITION BY ZONES, ON
 CALCULATIONS ONLY. PER 2004 FBC 13-607.1.ABC.1.
  
 4) THE RETURN AIR MAY NOT BE TAKEN FROM THE KITCHEN,
 PER 2004 FBC/R M1601.6.4.5 (A RETURN AIR DUCT MAY BE
 RAN TO THE DINING ROOM).
  
 5) PLEASE ADD AN EQUIPMENT SCHEDULE TO THE PLAN SHOWING
 THE PERTINENT INFORMATION FOR THE NEW AIR HANDLER, PER
 2004 W.P.B. AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]