2008-08-14 11:55:30 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SEE MECHANICAL PLAN PAGE M-1. PLEASE MAKE THE FLOOR | | PLAN OF THE HOUSE DARKER AS OUR ELECTRONIC SCANNER FOR | | RECORD RETENTION WILL NOT BE ABLE TO RECORD IT, PER | | 2004 W.P.B. AMEND. 106.1.3. | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | 13-101.2.2. SHORT FORM 600C-04 MAY BE USED AS THE | | ADDITION IS UNDER 600 SQ. FT., SEE 2004 FBC | | 13-600.3.C. | | | | 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS FOR THE | | ADDITION, IF SUBMITTED FOR THE WHOLE HOUSE PLEASE | | SEPARATE EXISTING HOUSE FROM ADDITION BY ZONES, ON | | CALCULATIONS ONLY. PER 2004 FBC 13-607.1.ABC.1. | | | | 4) THE RETURN AIR MAY NOT BE TAKEN FROM THE KITCHEN, | | PER 2004 FBC/R M1601.6.4.5 (A RETURN AIR DUCT MAY BE | | RAN TO THE DINING ROOM). | | | | 5) PLEASE ADD AN EQUIPMENT SCHEDULE TO THE PLAN SHOWING | | THE PERTINENT INFORMATION FOR THE NEW AIR HANDLER, PER | | 2004 W.P.B. AMEND. 106.3.5.4 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|