2008-09-25 09:34:46 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE KNOW |
| THAT THE RESUBMITTED GAS ISOMETRIC HAS A DIFFERENT |
| DESIGN FROM THE ORIGINAL REVIEWED. PLEASE KNOW THAT THE |
| FOLOWING COMMENTS ARE FOR SHEET P-1 GAS ISOMETRIC. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| *NOTE: THE RESUBMITTED GAS ISOMETRIC DOES NOT INDICATE |
| CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. |
| PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS |
| INDICATING THIS. |
| |
| 2. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| *NOTE: THE RESUBMITTED GAS ISOMETRIC IS INDICATING A |
| TOTAL DISTANCE OF 7'-0", HOWEVER THERE IS NO WAY TO |
| VERIFY THE TOTAL DISTANCE WITHOUT COMMENT #1 BEING |
| ADDRESSED. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |