Plan Review Notes
Plan Review Notes For Permit 08080212
Permit Number 08080212
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-18 15:53:52 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 200 AMP SERVICE IS ADEQUATE HOWEVER THE LOAD
 CALCULATIONS AT 153 AMPS ALL SEEMS TO BE IN THE 100 AMP
 PANEL "B". SEE SHEET E-2. VIOLATION OF ARTICLE 408.30 "
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THE
 MINIMUM FEEDER CAPACITY REQUIRED FOR THE LOAD
 CALCULATED IN ACCORDANCE WITH ARTICLE 220".THE
 CONDUCTORS ARE ALSO TOO SMALL FOR THE LOAD PER 310.16.
  
 2} CIRCUIT 1,3 FOR THE "EXISTING A/C" HAS A 5.8 KW
 LOAD, #8 WIRE ON A 60 AMP OCP. 5800/240=24 AMPS X 1.25%
 (ARTICLE 424.3(B) )=30.2 AMPS.PER 240.6(A) A 35 AMP
 BREAKER WOULD BE THE MAXIMUM PERMITTED.ALSO SEE SHEET
 M-1 INDICATING A NEW 5 KW AIR HANDLER IS TO BE
 INSTALLED.CORRELATE THE SHEETS WITH THE CORRECT
 INFORMATION.
  
 3} CIRCUIT #30, PANEL "B" IS LISTED AS LAUNDRY BUT
 APPEARS TO BE A SMALL APPLIANCE CIRCUIT ON SHEET
 E-1.PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718