2008-08-21 17:30:28 | RESIDENTIAL (R3) ADDITION AND RENOVATION BUILDING |
| REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTYTO VERIFY IF |
| IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY |
| OF PAID RECEIPT IF FEES ARE DUE. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-101.2.2 FBC 2004. |
| NOTE: PLEASE MAKE SURE CORRECT REVISED FORM IS USED |
| AND IS FILLED COMPLETELY TO AVOID UNNECESSARY DELAYS. |
| |
| 3-PLANS TO SPECIFY SAFETY GLASS FOR WINDOWS BY |
| BREAKFAST AREA AND BY SHOWER AREA AS REQUIRED BY SEC. |
| R308.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A)FIXED ARCHED WINDOW. SEE PLANS. |
| |
| B) WINDOW MULLION. SEEPLANS. |
| |
| C) SINGLE HUNG WINDOWS. NEED TO PROVIDE PRODUCT |
| APPROVAL THAT MEETS ALL THE DESIGN PRESSURES CALCULATED |
| FOR WINDOW W2. |
| |
| D) FLAT ROOF: |
| (1) SPECIFYSPECIFIC APPROVED ASSEMBLY TO BE USED. |
| |
| (2) SPECIFY SPECIFIC BASE SHEET FASTENING OPTION TO |
| BE USED. |
| (3) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING |
| AT PERIMETER &CORNER AREAS AS REQ'D BY GENERAL |
| LIMITATION #7 ONNOA 07-0111.03. |
| |
| 5- SHEET SP-1:DESIGN CRITERIA CALLS FOR EXPOSURE "C", |
| WHILE STRUCTURAL SHEETSS-1 AND S-3 CALL FOR EXPOSURE |
| "B". REVISE AS REQUIRED TO MATCH. |
| |
| 6- SHEET A-1: |
| A) CRAWL SPACE VENTILATION TO COMPLY WITH THE |
| MINIMUM SIZE,LOCATION AND ACCESS REQUIREMENTS OF SEC. |
| R408 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS |
| REQUIRED. |
| NOTE:REVISE EXTERIOR ELEVATIONS TO REFLECT LOCATION |
| OF VENTS AS WELL. |
| |
| B) REVISE UNDER FLOOR VENTILATION NOTES:REFERENCE |
| CODE SECTIONSFROM THE FLORIDA RESIDENTIAL CODE, NOT |
| FROM THEFBC. |
| |
| C) REVISE RISER TREAD RATIO TO COMPLY WITH SEC. |
| R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| NOTE: REVISE THIS INFORMATION ON STRUCTURAL DRAWINGS |
| ALSO. |
| |
| 7- SHEET A-2: |
| A) EMERGENCY ROOF DRAIN SCUPPERS TO COMPLY WITH |
| SEC. R903.4.1 OF 2004 FLORIDA RESIDENTIAL CODE. SPECIFY |
| HEIGHT FROM THE FINISHED ROOF COVERING. |
| |
| B) REVISE ROOF DRAINAGE NOTES:REFERENCE CODE |
| SECTIONSFROM THE 2004 FLORIDA RESIDENTIAL CODE, NOT |
| THE 2004 FBC. |
| |
| 8- SHEET A-4: |
| A) TYPICAL WALL SECTION: |
| (1) CLARIFY WHYVENTING IS NOT REQUIRED. SPECIFY |
| WHICH CODE SECTIONS STATES THAT NO VENTILATION IS |
| REQUIRED ON ROOF.ACCORDING TO SEC. R806 OF 2004 |
| FLORIDA RESIDENTIAL CODECROSS VENTILATION IS |
| REQUIRED. SPECIFYIN PLANS/ELEVATIONS SIZE AND |
| LOCATION OF CROSS VENTILATION. |
| |
| (2) SPECIFYHOW PROVIDING PROTECTION TO THE FLOOR |
| JOIST AS REQUIRED BY SEC. R319 .1 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| (3) REVISE SIZE OF FLOOR JOIST TO MATCH SIZE SHOWN |
| ON STRUCTURAL PLANS. |
| |
| 9- SHEET S-2:REVISE NOTES ON TYPICAL WIND PRESSURE |
| BOX SHOWN ON THE FLOOR PLAN D.DISTANCE "A" TO BE |
| 4'-0" MIN. AS REQUIRED BY NOTE A ON FIGURE R301.2(8) OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| ***NOTE:REVISE SAME INFORMATION ON SHEET S-3. |
| |
| 10- OWES $5.02 FOR RADON FEES FOR NEW ADDITION. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |