Plan Review Notes
Plan Review Notes For Permit 08080208
Permit Number 08080208
Review Stop B
Sequence Number 2
Notes
Date Text
2008-08-29 11:14:48****CORRECTIONS****
 ****PLANS ROUTED TO BE ISSUED***
 ****INFORMATIONAL FOR CONTRACTOR TO ASSIST IN
 COMPLETING INSTALLATION SCHEDULE PROPERLY. PLANS ROUTED
 TO BE ISSUED***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ADDRESSED.
  
 2. FOR THE ACCORDIONS, PLEASE COMPLETE THE INSTALLATION
 SCHEDULE. THE ANCHOR SPACING WAS NOT COMPLETED ON THE
 SECOND PAGE.
  
 3. PLEASE REVISE SHUTTER CONNECTION MOUNTING TYPE TO
 CORRELATE WITH THE ANCHOR SCHEDULE. FOR INSTANCE, C1
 THROUGH C5. YOU'VE SPECIFIED WALL, BUT CIRCLED TWO
 DIFFERENT ANCHOR TYPES AND TWO DIFFERENT ANCHORS ON
 SHEET 3, CLEAR PANEL PRODUCT APPROVAL. CIRCLING ITEMS
 ON THE PRODUCT APPROVAL CAN BE HELPFUL FOR
 REVIEW/INSPECTIONS BUT MUST CORRELATE WITH THE JOB AND
 THE INSTALLATION SCHEDULE.
  
 2ND REVIEW, NOT ADDRESSED. ALL STILL SAY "WALL"; PLEASE
 REVISE. FOR EXAMPLE, STORM PANELS 2250 SPECIFY 7"
 SPACING, SUBSTRATE IS NOT COMPLETED BUT "MASONRY"
 CHECKED AT THE TOP. SHEET 5 OF THE PRODUCT APPROVAL,
 CANNOT DETERMINE WHICH MOUNTING TYPE YOU ARE USING BUT
 EACH HAS A DIFFERENT REQUIREMENT AND 7" IS NOT
 COMPLIANT FOR ANY OF THEM.
  
 CLEAR PANELS, STATE "WALL", NO SUBSTRATE INFORMATION
 PROVIDED. THE PRODUCT APPROVAL HAS C1 AND C4 CIRCLED.
 13" APPEARS COMPLIANT IF THE SUBSTRATE IS CONCRETE, BUT
 NOT FOR MASONRY. PLEASE SPECIFY SUBSTRATE AND CLARIFY
 CONNECTION TYPE.
  
  
  
  
  
  
  