2008-08-29 11:14:48 | ****CORRECTIONS**** |
| ****PLANS ROUTED TO BE ISSUED*** |
| ****INFORMATIONAL FOR CONTRACTOR TO ASSIST IN |
| COMPLETING INSTALLATION SCHEDULE PROPERLY. PLANS ROUTED |
| TO BE ISSUED*** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. ADDRESSED. |
| |
| 2. FOR THE ACCORDIONS, PLEASE COMPLETE THE INSTALLATION |
| SCHEDULE. THE ANCHOR SPACING WAS NOT COMPLETED ON THE |
| SECOND PAGE. |
| |
| 3. PLEASE REVISE SHUTTER CONNECTION MOUNTING TYPE TO |
| CORRELATE WITH THE ANCHOR SCHEDULE. FOR INSTANCE, C1 |
| THROUGH C5. YOU'VE SPECIFIED WALL, BUT CIRCLED TWO |
| DIFFERENT ANCHOR TYPES AND TWO DIFFERENT ANCHORS ON |
| SHEET 3, CLEAR PANEL PRODUCT APPROVAL. CIRCLING ITEMS |
| ON THE PRODUCT APPROVAL CAN BE HELPFUL FOR |
| REVIEW/INSPECTIONS BUT MUST CORRELATE WITH THE JOB AND |
| THE INSTALLATION SCHEDULE. |
| |
| 2ND REVIEW, NOT ADDRESSED. ALL STILL SAY "WALL"; PLEASE |
| REVISE. FOR EXAMPLE, STORM PANELS 2250 SPECIFY 7" |
| SPACING, SUBSTRATE IS NOT COMPLETED BUT "MASONRY" |
| CHECKED AT THE TOP. SHEET 5 OF THE PRODUCT APPROVAL, |
| CANNOT DETERMINE WHICH MOUNTING TYPE YOU ARE USING BUT |
| EACH HAS A DIFFERENT REQUIREMENT AND 7" IS NOT |
| COMPLIANT FOR ANY OF THEM. |
| |
| CLEAR PANELS, STATE "WALL", NO SUBSTRATE INFORMATION |
| PROVIDED. THE PRODUCT APPROVAL HAS C1 AND C4 CIRCLED. |
| 13" APPEARS COMPLIANT IF THE SUBSTRATE IS CONCRETE, BUT |
| NOT FOR MASONRY. PLEASE SPECIFY SUBSTRATE AND CLARIFY |
| CONNECTION TYPE. |
| |
| |
| |
| |
| |
| |
| |