Plan Review Notes For Permit 08080165 |
Permit Number |
08080165 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-08-29 16:51:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED (SAME PLANS | | SUBMITTED) | | | | 1. DECLARE DESIGN PRESSURES. INDICATE ON THE PRODUCT | | APPROVAL WHICH OPTION YOU WILL BE USING AS THEY HAVE | | DIFFERENT DESIGN PRESSURES. | | | | 2. INDICATE WHICH MULLION YOU PROPOSE TO USE AS EACH | | OPTION HAS DIFFERENT DESIGN PRESSURES. | | | | 3. ENGINEERING MAY BE REQUIRED TO JUSTIFY DESIGN | | PRESSURES USED, FBC1609. THAT REQUIREMENT CANNOT BE | | DETERMINED AT THIS TIME UNTIL DESIGN PRESSURES ARE | | DECLARED. |
|