2008-08-15 15:24:53 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THERE ARE TWO DIFFERENT VENT PIPE SIZES BEING |
| INDICATED FOR THE ENTRAPMENT AVOIDANCE. THE ENTRAPMENT |
| AVOIDANCE VENT PIPE ANALYSIS-MAXIMUM LENGTH DETAIL IS |
| INDICATING A 1" VENT FOR THE DETAIL, HOWEVER SHEET 2, |
| POOL PIPING DIAGRAM IS INDICATING AN 1-1/2" VENT PIPE. |
| PLEASE CORRELATE THE PLAN SHEET AND DETAIL VENT PIPING |
| SIZE. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC-2004 |
| RESIDENTIAL, CHAPTER 41, SECTION R4101.6 ENGINEERING |
| DESIGN. |
| |
| 2. A POOL HEATER IS BEING INDICATED ON THE PERMIT |
| APPLICATION AND ON SHEET 2, PLUMBING PIPING DIAGRAM, |
| HOWEVER IT IS NOT BEING INDICATED ON THE SPECIFICATION |
| POOL EQUIPMENT. PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| PER (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS AND FBC-2004 RESIDENTIAL, |
| CHAPTER 41, SECTION R4101.6 ENGINEERING DESIGN. |
| |
| 3. FBC-2004 SEC. 424.2.14.1, OR |
| FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| SHEETS REQUIRED, PLEASE SUBMIT) |
| |
| 4. FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF.(MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT) |
| |
| 5. FBC-2004 SEC. 424.2.7.2, OR |
| FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| EQUIPMENT SHALL BE MOUNTED ON A |
| SUBSTANTIAL BASE IN A MANNER THAT WILL |
| ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| BE A NOMINAL 4" THICK. (DETAIL REQUIRED) |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |