Plan Review Notes
Plan Review Notes For Permit 08080134
Permit Number 08080134
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-18 11:27:59PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2, FLOOR PLAN: THE CLEAR FLOOR SPACE FOR THE
 S-1 SINK IN THE LOUNGE IS BEING INDICATED WRONG. PER
 FBC-2004 CHAPTER 11, SECTION 11-4.24.5 CLEAR FLOOR
 SPACE SHALL BE 30" X 48" AND CLEAR FLOOR SPACE SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH SINK. PLEASE PROVIDE
 AN ELEVATION DETAIL WITH THE OTHER FOLLOWING
 REQUIREMENTS FOR THE ACCESSIBLE SINK PER FBC- 2004
 CHAPTER 11 SECTIONS.
  
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
  
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
  
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. SINK CABINETS SHALL BE OPEN FRONT FOR SINK,
 PLEASE REFERENCE COMMENT #1..
  
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
  
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEET 3, SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THE SIZE OF THE FIXTURE DRAINS AND TRAPS FOR
 THE PROPOSED EWC DRINKING FOUNTAIN AND S-1 SINK. PLEASE
 KNOW THAT THE RELOCATED S-1 SINK FIXTURE DRAIN SHALL BE
 2 INCH (2") WITH AN 1-1/2 INCH (1-1/2") TRAP. PER
 FBC-2004 PLUMBING TABLE 906.1 MAXIMUM DISTANCE OF
 FIXTURE TRAPS FROM VENT. PER (W.P.B. AS AMENDED)
 SECTION 106.3.5.1.3 PLUMBING (4)(13).
  
 3. NOTE: A POTABLE WATER ISOMETRIC RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED EWC DRINKING FOUNTAIN AND S-1
 SINK. CLEARLY INDICATE THE PIPE SIZE PER FBC-2004
 PLUMBING SECTION 601.1 SCOPE, A WATER HAMMER ARRESTOR
 FOR THE REF. ICE MAKER PER FBC-2004 PLUMBING SECTION
 604.9 WATER HAMMER, AND CLEARLY INDICATE THAT THERE IS
 AN EXISTING BACKFLOW PREVENTER PER FBC-2004 PLUMBING
 SECTION 608 PROTECTION OF POTABLE WATER SUPPLY. PER
 (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  