| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| THESE COMMENTS RELATE ONLY TO THE AREA WHERE LIGHTING |
| CIRCUITS ARE BEING EXTENDED, ADDED OR CHANGED. |
| |
| 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR |
| LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE |
| ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| CALCULATION PROCEDURES, GENERAL. |
| THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| METHOD DESCRIBED IN SECTION 415.2.B.1.THE INSTALLED |
| INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| DENSITY REQUIREMENTS.INDICATE WATTAGES ON THE FIXTURE |
| SCHEDULE. |
| |
| 2} 13-415.1.ABC.1.2 SPACE CONTROL. |
| EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| |
| |
| SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE |
| PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS. |
| |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |