 1)THE INSTALLATION SCHEDULE AND THE PRODUCT APPROVAL
 DO NOT CORRESPOND WITH EACH OTHER. PAGE #6 OF THE
 PRODUCT APPROVAL INDICATE USING CONNECTION TYPE 'A' AND
 'D' AND ON SHEET #7 'H'. THE ANCHOR SPACING INDICATED
 ON YOUR INSTALLATION IS 10 AND 12 INCHES. ACCORDING THE
 PRODUCT APPROVAL PAGE #13, THE ANCHOR SPACING FOR
 CONNECTION TYPE (D) WAS NOT INDICATED, HOWEVER THE
 SPACING FOR (D) SHALL BE 9 INCHES WHICH IS NOT SHOWN ON
 THE INSTALLATION SCHEDULE. ON PAGE #14 THE ANCHOR
 SPACING INDICATED IS 8.5 INCHES FOR CONNECTION TYPE (H)
 THIS INFORMATION IS ALSO MISSING FROM THE INSTALLATION
 SCHEDULE.
  
 2)THE PRODUCT APPROVAL FOR THE TRANSPARENT PANELS
 DOES NOT INDICATE THE TYPE OF ANCHORS TO BE USED, THE
 EDGE DISTANCE OR THE ANCHOR SPACING. SEE SHEET #3 OF
 THE PRODUCT APPROVAL. THE EDGE DISTANCE FOR BOTH TYPES
 OF SHUTTERS SHALL BE INDICATED ON YOUR INSTALLATION
 SCHEDULE. PLEASE SEE AN EXAMPLE OF THE INSTALLATION
 SCHEDULE AND PROCEDURES IN THE PACKAGE. PLEASE MAKE
 SURE THE PRODUCT APPROVALS ARE ATTACHED, THE LOOSE
 PAGES ARE NOT ACCEPTABLE.
  