2008-08-08 08:21:57 | | | | | | | 1)THE INSTALLATION SCHEDULE AND THE PRODUCT APPROVAL | | DO NOT CORRESPOND WITH EACH OTHER. PAGE #6 OF THE | | PRODUCT APPROVAL INDICATE USING CONNECTION TYPE 'A' AND | | 'D' AND ON SHEET #7 'H'. THE ANCHOR SPACING INDICATED | | ON YOUR INSTALLATION IS 10 AND 12 INCHES. ACCORDING THE | | PRODUCT APPROVAL PAGE #13, THE ANCHOR SPACING FOR | | CONNECTION TYPE (D) WAS NOT INDICATED, HOWEVER THE | | SPACING FOR (D) SHALL BE 9 INCHES WHICH IS NOT SHOWN ON | | THE INSTALLATION SCHEDULE. ON PAGE #14 THE ANCHOR | | SPACING INDICATED IS 8.5 INCHES FOR CONNECTION TYPE (H) | | THIS INFORMATION IS ALSO MISSING FROM THE INSTALLATION | | SCHEDULE. | | | | 2)THE PRODUCT APPROVAL FOR THE TRANSPARENT PANELS | | DOES NOT INDICATE THE TYPE OF ANCHORS TO BE USED, THE | | EDGE DISTANCE OR THE ANCHOR SPACING. SEE SHEET #3 OF | | THE PRODUCT APPROVAL. THE EDGE DISTANCE FOR BOTH TYPES | | OF SHUTTERS SHALL BE INDICATED ON YOUR INSTALLATION | | SCHEDULE. PLEASE SEE AN EXAMPLE OF THE INSTALLATION | | SCHEDULE AND PROCEDURES IN THE PACKAGE. PLEASE MAKE | | SURE THE PRODUCT APPROVALS ARE ATTACHED, THE LOOSE | | PAGES ARE NOT ACCEPTABLE. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|