2008-10-07 16:10:24*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1). SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT HAS BEEN FILED FOR RECORDING,
 ALONG WITH A COPY THEREOF.
  
 3). PAGE 1 OT THE HYDRAULIC CALCULATIONS (PAGE 1)
 REFERENCE THE SOURCE OF INFORMATION (FOR THE FLOW TEST
 INFO) AS TVA FIRE & LIFE SAFETY.
  
 *NEW COMMENTS:
  
 A.) PLEASE INCLUDE THE ORIGINAL APPLICATION WITH YOUR
 SUBMITTALS.
  
 B.) PLAN SHEET FP-2 (2 OF 2) WAS NOT INCLUDED IN THE
 SUBMITTAL AND THEREFORE COULD NOT BE REVIEWED FOR
 COMPLIANCE.
  
 C.) PLEASE BE ADVISED THAT THE PLANS ARE TO SUBMITTED
 AS A "RESUB" AND NOT AS A "REVISION" (SINCE A PERMIT
 HAS NOT YET BEEN ISSUED FOR THIS SCOPE OF WORK)).
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722