Plan Review Notes
Plan Review Notes For Permit 08070905
Permit Number 08070905
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-18 10:35:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SPAN IS NOT CORRECT.OPENING 1, A 3' SPAN IS SHOWN
 FOR A 60" HIGH OPENING WITH A 3.5" EDGE DISTANCE,
 VERTICAL INSTALLATION.9' SPAN SPECIFIED FOR OPENIGNS
 5 AND 6, 6" ANCHOR SPACING REQUIRED, SEE PAGE 12 OF
 PRODUCT APPROVAL.PLEASE REVISE SPANS AND ANCHOR
 SPACING IF NECESSARY.
  