Plan Review Notes
Plan Review Notes For Permit 08070866
Permit Number 08070866
Review Stop E
Sequence Number 3
Notes
Date Text
2008-10-10 09:20:46 
 ** DENIED 3RD REVIEW**
  
 SCOPE OF WORK ON PLANS HAS NOW ONCE AGAIN BEEN REVISED
 CREATING NEW COMMENTS. THE PLANS/PACKAGE ALSO STILL
 CONTAINS COMMENTS FROM PREVIOUS REVIEW WHICH HAVE STILL
 NOT BEEN ADDRESSED. SEE THE FOLLOWING NOTES.
  
 1) NOTE: SCOPE OF WORK IS CONFUSING ONCE AGAIN. PERMIT
 APPLICATION AND NOTE ON PLANS MENTIONS TO ADD DEVICES
 FOR ELEVATOR RE-CALL ONLY YET THIS DOES NOT
 COORDINATION WITH OTHER NOTES ON PLANS AND DOCUMENTS IN
 PACKAGE. THE PACKAGE OF DOCUMENTS ONCE AGAIN SUBMITTED
 SHOWS A NEW FIRE ALARM PANEL. HOWEVER THE PLANS AND
 APPLICATION HAS BEEN REVISED STATING RECALL ONLY TO
 EXISTING FIRE ALARM PANEL. WHAT SCOPE OF WORK IS BEING
 DONE???
 THE PLANS SHOW OTHER DEVICES ON THE SYMBOL LEGEND SUCH
 AS RELAYS BEING ADDED TO EXISTING PULL STATIONS HOWEVER
 THESE SYMBOLS WHICH WERE ON PREVIOUS PLANS HAVE NOW
 BEEN REMOVED. IN FACT MOST OF THE ITEMS SHOWN ON
 PREVIOUS PLANS HAVE BEEN REMOVED. THESE P/R SYMBOLS ARE
 SHOWN ON RISER HOWEVER NOT ON PLANS.
  
  
 2) NOTE: PLANS ARE NOW SIGNED, DATED AND SEALED BY A
 NEW DESIGN PROFESSIONAL.
  
 3) NOTE: PACKAGE OF DOCUMENTS ETC WILL BE KEPT SO THAT
 A MEETING BETWEEN THE CONTRACTOR AND THE CITY CAN BE
 HAD BEFORE PICKING UP PLANS.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  