2008-10-10 09:20:46 | |
| ** DENIED 3RD REVIEW** |
| |
| SCOPE OF WORK ON PLANS HAS NOW ONCE AGAIN BEEN REVISED |
| CREATING NEW COMMENTS. THE PLANS/PACKAGE ALSO STILL |
| CONTAINS COMMENTS FROM PREVIOUS REVIEW WHICH HAVE STILL |
| NOT BEEN ADDRESSED. SEE THE FOLLOWING NOTES. |
| |
| 1) NOTE: SCOPE OF WORK IS CONFUSING ONCE AGAIN. PERMIT |
| APPLICATION AND NOTE ON PLANS MENTIONS TO ADD DEVICES |
| FOR ELEVATOR RE-CALL ONLY YET THIS DOES NOT |
| COORDINATION WITH OTHER NOTES ON PLANS AND DOCUMENTS IN |
| PACKAGE. THE PACKAGE OF DOCUMENTS ONCE AGAIN SUBMITTED |
| SHOWS A NEW FIRE ALARM PANEL. HOWEVER THE PLANS AND |
| APPLICATION HAS BEEN REVISED STATING RECALL ONLY TO |
| EXISTING FIRE ALARM PANEL. WHAT SCOPE OF WORK IS BEING |
| DONE??? |
| THE PLANS SHOW OTHER DEVICES ON THE SYMBOL LEGEND SUCH |
| AS RELAYS BEING ADDED TO EXISTING PULL STATIONS HOWEVER |
| THESE SYMBOLS WHICH WERE ON PREVIOUS PLANS HAVE NOW |
| BEEN REMOVED. IN FACT MOST OF THE ITEMS SHOWN ON |
| PREVIOUS PLANS HAVE BEEN REMOVED. THESE P/R SYMBOLS ARE |
| SHOWN ON RISER HOWEVER NOT ON PLANS. |
| |
| |
| 2) NOTE: PLANS ARE NOW SIGNED, DATED AND SEALED BY A |
| NEW DESIGN PROFESSIONAL. |
| |
| 3) NOTE: PACKAGE OF DOCUMENTS ETC WILL BE KEPT SO THAT |
| A MEETING BETWEEN THE CONTRACTOR AND THE CITY CAN BE |
| HAD BEFORE PICKING UP PLANS. |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |