Plan Review Notes For Permit 08070866 |
Permit Number |
08070866 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-09-24 15:16:27 | ***DENIED*** | | | | SOME OF THE COMMENTS HAVE BEEN ADDRESSED. PLEASE SEE | | THE FOLLOWING: | | | | 1) THERE STILL EXISTS SOME UNCERTAINTY AS TO THE SCOPE | | OF WORK. THE PLANS INDICATE ELEVATOR RECALL ONLY BUT | | OTHER EQUIPMENT IS ILLUSTRATED. PLEASE CLARIFY. | | | | 2) WORK SHALL COMPLY WITH NFPA 72. PLEASE ADD NOTE TO | | PLANS. | | | | 3) PLANS TO COMPLY WITH REQUIREMENTS OF FBC 106.1.1 AND | | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF PROPOSED WORK. | | | | 4) OK | | | | 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | PLEASE ADD NOTE TO PLANS. | | | | 6) OK | | | | 7) PLEASE CLARIFY IF THIS IS A NEW FIRE ALARM SYSTEM AS | | PLANS SEEM TO SUGGEST NEW EQUIPMENT AND FIRE ALARM | | PANEL. AN APPROVED PLAN FOR FIRE RESCUE NOTIFICATION IS | | ACCEPTABLE IN EXISTING INSTALLATIONS. SEC. 9.6.4.3. | | OTHERWISE THE SYSTEM SHALL MEET THE REQUIREMENTS OF | | SEC. 31.3.4 AND SEC. 9.6. | | | | PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING FLORIDA | | STATUTES REQUIREMENTS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|