Notes
Date Text
2008-09-23 08:56:04 
 ** DENIED 2 REVIEW **
  
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION. THE SCOPE OF
 WORK WAS REVISED HOWEVER AS PER CONVERSATION MR.
 CEPILETTO THE FIRE ALARM PANEL WAS ALSO BEING CHANGED
 OUT AS THE EXISTING PANEL WOULD NOT SUPPORT THE NEW
 SYSTEM. THE SUBMITTED PACKAGE STILL CONTAINS DOCUMENTS
 FOR NEW FIRE ALARM PANEL. PLEASE COORDINATE ALL PLANS,
 DOCUMENTS, PERMIT APPLICATION FOR COMPLETE SCOPE OF
 WORK. 106.1
  
 2) NOTE: PLEASE SEE THE SUBMITTED PLANS AS THE PLANS
 CONTAIN CHANGES MADE AND PHOTO-COPIES OF THE PREVIOUSLY
 DATED, SIGNED AND SEALED PLANS. IT IS A VIOLATION OF
 FLORIDA STATUTES 471.025 TO MAKE CHANGES TO PLANS WHICH
 ARE SIGNED AND SEALED BY ENGINEER AND MAKE PHOTO-COPIES
 OF HIS/HER WORK AND USE FOR ANY PURPOSE.
 THREE SETS OF PLANS WERE SUBMITTED AND ALL THREE SETS
 ARE PHOTO-COPIES OF THE ORIGINAL SIGNED AND SEALED
 PLANS WITH CHANGES MADE OVER PLANS.
 ** TWO SETS WILL BE RETAINED BY THIS OFFICE AND PLACED
 WITH PREVIOUS PLANS RETAINED.
 FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE THE CANDELA RATING AS NOTED ON
 PLANS DOES NOT THE MINIMUM LEVEL FOR ADA IN THE FBC
 11-4.28.3(4).
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 5) NOTE: THE PLANS DO NOT CONTAIN ANY MINIMUM DESIGN
 CODES. FOR EXAMPLE: THE FLORIDA BUILDING CODE, NFPA-72
 2002, NFPA-70 2005. WHAT CODES IS THIS SYSTEM DEISGNED
 UNDER? FLORIDA STATUTES 553.73 LATEST ADOPTED MINIMUM
 CODES ARE LISTED IN THE 2007 REVISIONS TO THE 2004 FBC.
 PLEASE BE SURE TO SUBMIT THE PLANS WIHT REFERENCE TO
 MINIMUM CODES AND DEISGNS.
  
 6) NOTE: PLEASE SEE FBC FOR PULL STATIONS MINIMUM
 DEVICE HEIGHTS. (PULL STATIONS) PLANS NOW SHOW FOR THE
 FIRST TIME DEVICE HEIGHTS. PLEASE SEE FBC CHAPTER 11
 FOR ADA COMPLIANCE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  