2008-09-23 08:56:04 | |
| ** DENIED 2 REVIEW ** |
| |
| |
| 1) NOTE: PLEASE SEE PERMIT APPLICATION. THE SCOPE OF |
| WORK WAS REVISED HOWEVER AS PER CONVERSATION MR. |
| CEPILETTO THE FIRE ALARM PANEL WAS ALSO BEING CHANGED |
| OUT AS THE EXISTING PANEL WOULD NOT SUPPORT THE NEW |
| SYSTEM. THE SUBMITTED PACKAGE STILL CONTAINS DOCUMENTS |
| FOR NEW FIRE ALARM PANEL. PLEASE COORDINATE ALL PLANS, |
| DOCUMENTS, PERMIT APPLICATION FOR COMPLETE SCOPE OF |
| WORK. 106.1 |
| |
| 2) NOTE: PLEASE SEE THE SUBMITTED PLANS AS THE PLANS |
| CONTAIN CHANGES MADE AND PHOTO-COPIES OF THE PREVIOUSLY |
| DATED, SIGNED AND SEALED PLANS. IT IS A VIOLATION OF |
| FLORIDA STATUTES 471.025 TO MAKE CHANGES TO PLANS WHICH |
| ARE SIGNED AND SEALED BY ENGINEER AND MAKE PHOTO-COPIES |
| OF HIS/HER WORK AND USE FOR ANY PURPOSE. |
| THREE SETS OF PLANS WERE SUBMITTED AND ALL THREE SETS |
| ARE PHOTO-COPIES OF THE ORIGINAL SIGNED AND SEALED |
| PLANS WITH CHANGES MADE OVER PLANS. |
| ** TWO SETS WILL BE RETAINED BY THIS OFFICE AND PLACED |
| WITH PREVIOUS PLANS RETAINED. |
| FAC 61G15-23.002 |
| |
| 3) NOTE: PLEASE SEE THE CANDELA RATING AS NOTED ON |
| PLANS DOES NOT THE MINIMUM LEVEL FOR ADA IN THE FBC |
| 11-4.28.3(4). |
| |
| 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| NOTICE GIVEN AT THIS TIME. |
| |
| 5) NOTE: THE PLANS DO NOT CONTAIN ANY MINIMUM DESIGN |
| CODES. FOR EXAMPLE: THE FLORIDA BUILDING CODE, NFPA-72 |
| 2002, NFPA-70 2005. WHAT CODES IS THIS SYSTEM DEISGNED |
| UNDER? FLORIDA STATUTES 553.73 LATEST ADOPTED MINIMUM |
| CODES ARE LISTED IN THE 2007 REVISIONS TO THE 2004 FBC. |
| PLEASE BE SURE TO SUBMIT THE PLANS WIHT REFERENCE TO |
| MINIMUM CODES AND DEISGNS. |
| |
| 6) NOTE: PLEASE SEE FBC FOR PULL STATIONS MINIMUM |
| DEVICE HEIGHTS. (PULL STATIONS) PLANS NOW SHOW FOR THE |
| FIRST TIME DEVICE HEIGHTS. PLEASE SEE FBC CHAPTER 11 |
| FOR ADA COMPLIANCE. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |