Plan Review Notes For Permit 08070866 |
Permit Number |
08070866 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-13 15:54:57 | ***DENIED*** | | | | 1) MORE INFORMATION REQUIRED FOR COMPLETE FIRE PLAN | | REVIEW. PLEASE INDICATE SCOPE OF WORK. | | | | 2) WORK SHALL COMPLY WITH NFPA 72, 2002. | | | | 3) PLANS TO COMPLY WITH REQUIREMENTS OF FBC 106.1.1. | | AND SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE | | LOCATION, NATURE AND EXTENT OF PROPOSED WORK. | | | | 4) PLEASE INDICATE OCCUPANCY CLASSIFICATION FOR | | BUILDING PER NFPA 101, CHAPTER-6. | | | | 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. | | | | 6) PLEASE INDICATE IF BUILDING IS CURRENTLY PROTECTED | | BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | 7) SINCE THIS IS A NEW INSTALLATION, WILL FIRE ALARM BE | | MONITORED AS THIS IS NOT SHOWN ON PLANS? NFPA 101, SEC. | | 31.3.4. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|