Plan Review Notes For Permit 08070863 |
Permit Number |
08070863 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-01 16:29:46 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEWCHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- ACCORDING TO PERMIT APPLICATION DESCRIPTION, THERE | | ARE TWO SLIDING GLASS DOORS THAT WILL RECEIVE STORM | | PANELS TOO. OPENING SIZES SHOWN ON THE INSTALLATION | | SCHEDULE DON'T REFLECT ANY BIG OPENIGS FOR SLIDING | | GLASS DOORS. REVISE/CLARIFY AS REQUIRED.ALL OPENINGS | | CORRESPOND TO WINDOW OPENINGS. | | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | SEC. 713.13FLORIDA STATUTE. | | | | 3- CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC MOUNTING | | CONDITIONS (EG: DIRECT MOUNT OR BUILT OUT)TO VERIFY | | COMPLIANCE WITH MINIMUM PANEL LENGTH AS REQUIRED BY | | TABLE 2ONSHEET 6 OF 6 OF DRAWING 05-329 SUBMITTED. | | OTHERWISE COMPLETE ENGINEERING WILL BE REQUIRED. SEE | | TABLE 2 NOTE ON SHEET 6 OF 6. | | | | 4- REVISE SHUTTER SPAN SIZE SHOWN ON INSTALLATION | | SCHEDULE.IF SHUTTERS ARE GOING TO BE INSTALLED WITH | | 3" MIN. EDGE DISTANCE, THEN SIZE OF PANELS SHOWN ON | | SHUTTER SPAN COLUMNNEED TO BE REVISED.IT CAN'T BE | | JUST 6" LONGER THAN THE OPENING.NEED TO CONSIDER THE | | STUCCO THICKNESS AND LOCATION OF ANCHOR ON THE STORM | | PANEL WHENSPECIFYING THE PANEL OVERALL LENGTH. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|