2008-08-15 10:45:29 | ***DENIED*** |
| |
| 1) PLANS SEEM TO SUGGEST SMOKE DETECTORS CONNECTED TO |
| THE FIRE ALARM SYSTEM THROUGHOUT THE GUEST SUITES. |
| PLEASE NOTE NFPA 101, SEC. 28.3.4.5 REQUIRESAPPROVED |
| SINGLE STATION SMOKE ALARMS IN EVERY GUEST ROOM AND |
| EVERY LIVING AREA AND SLEEPING ROOM. |
| |
| 2) NFPA 101, SEC. 28.3.4.2 (2) REQUIRES A MANUAL FIRE |
| ALARM BOX AT THE HOTEL DESK OR OTHER CENTRAL LOCATION |
| UNDER CONTINUOUS SUPERVISION BY RESPONSIBLE EMPLOYEES. |
| PLEASE ILLUSTRATE ON PLANS |
| |
| 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE |
| ADD NOTE TO PLANS |
| |
| 4) FIRE ALARM SHALL BE UL CERTIFICATED FOR CENTRAL |
| STATION SERVICE PRIOR TO FINAL INSPECTION. PLEASE ADD |
| NOTE TO PLANS |
| |
| 5) MORE INFORMATION REQUIRED WITH REGARD TO ELECTRIC |
| LOCKS. SPECIAL LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| NFPA 101, SEC. 7.2.1.6. ADDITIONALLY, SEPARATE SHOP |
| DRAWINGS AND PERMIT IS REQUIRED PRIOR TO INSTALLATION. |
| AT TIME OF PERMIT APPLICATION, MANUFACTURER |
| SPECIFICATION SHEETS REQUIRED. |
| |
| 6) ALL WORK TO COMPLY WITH NFPA 72, 2002. |
| |
| 7) PLEASE INDICATE TYPE OF DETECTION COVERAGE PER NFPA |
| 72 AS THERE DOES NOT APPEAR TO BE COVERAGE IN |
| ELECTRICAL, MECHANICAL, STORAGE AREAS ETC. |
| |
| 8) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. |
| |
| 9) PLEASE PROVIDE SEQUENCE OF OPERATION TO DRAWINGS. |
| |
| |
| MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |