2009-05-07 14:39:54**PROVISO PLANS**
  
  
  
 1) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULES.
  
 RTU FOR CIRCUITS L20,20,24 ON PANEL, HOWEVER NOT THE
 SAME ON PLANS
 RECEPTACLE IN TENANT SPACE NO CIRCUIT. ( NEXT TO A
 PANEL.)
 EM LIGHT IN TENANT SPACE WHICH SHOULD BE ON L PANEL IS
 SHOWN CIRCUITED TO A-29. MUST BE IN THE SAME TENANT.
 LIGHT FIXTURES IN OFFICES AND BATHROOM SHOW NOW
 CIRCUITS.
 OTHER CIRCUITS SUCH AS THE RECEPTACLES SHALL BE
 SPECIFIC. STATING *RECEPTACLES* IS NOT ACCEPTABLE.
 PLEASE SEE COMMENTARY IN THE 2005 NEC UNDER 408.4. FOR
 EXAMPLE: THE RECEPTACLES ALONG THE REAR WALL WOULD
 STATE JUST THAT; * RECEPTACLES REAR WALL* OR WORDS TO
 THAT SAME AFFECT.
  
 408.4, FBC 106.1.1, 106.3.5
  
 ** ANY AND ALL LOW VOLTAGE SHALL BE UNDER SEPARATE
 PERMITS, FEES AND PLANS.
  
 ** THE PLANS MUST BE UPDATED, SUBMITTED AS A REVISION
 AND ON-SITE BEFORE INSPECTIONS. PLEASE KEEP IN MIND,
 RE-INSPECTION FEES WILL BE ASSESSED PER BUILDING
 OFFICIAL IF PLANS ARE NOT REVISED BEFORE INSPECTIONS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  