Plan Review Notes
Plan Review Notes For Permit 08070835
Permit Number 08070835
Review Stop M
Sequence Number 2
Notes
Date Text
2008-11-12 11:56:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLAN MEP4 WAS NOT PART OF THE REVISED PLANS. PLEASE
 REVISE PLAN TO INCLUDE AN A/C EQUIPMENT SCHEDULE WITH
 ALL THE PERTINENT INFORMATION ON IT, PER 2004 FBC
 106.3.5.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS, PER 2004
 FBC/M 403.2.
  
 3) SUBMIT COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]