Plan Review Notes For Permit 08070835 |
Permit Number |
08070835 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-12-03 15:21:23 | ***DENIED*** | | | | SOME OF THE COMMENTS FROM THE FIRST REVIEW HAVE BEEN | | ADDRESSED. PLEASE SEE THE FOLLOWING COMMENTS: | | | | 1) PROVIDE COMPLETE ADDRESS INCLUDING NUMERICAL ON EACH | | SHEET SUBMITTED. | | | | 2) PLANS INDICATE THAT PROJECT WILL BE PROTECTED BY AN | | AUTOMATIC FIRE SPRINKLER SYSTEM. IN ADDITION TO THE | | SEPARATE SHOP DRAWINGS AND PERMIT, PLEASE SHOW | | SPRINKLER LAYOUT WITH THIS SUBMITTAL. SPRINKLERS MAY BE | | SHOWN ON REFELECTED CEILING PLAN. COMMENT TAKEN FROM | | FIRST REVIEW. | | | | 3) PLANS REFERENCE WORK TO COMPLY WITH NFPA 72, 2002. | | PLEASE CLARIFY IF BUILDING WILL BE PROVIDED WITH FIRE | | ALARM SYSTEM. INFORMATION INCLUDED SHOULD BE LIMITED TO | | WORK THAT IS RELEVANT TO THIS PROJECT. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|