Plan Review Notes For Permit 08070835
Permit Number 08070835
Review Stop E
Sequence Number 2
Notes
Date Text
2008-12-01 11:24:43 
 ** FAILED REVIEW
  
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE DONE
 UNDER THE INCORRECT VERSION NOT ADOPTED BY THE FBC.
 PLEASE SEE FBC 13-400.A.3
 PLEASE GO THE ENERGY GAUGE WEBSITE AS IT IS UNDERSTOOD
 BY THIS OFFICE THERE IS A PATCH AVAIL FOR THE CORRECT
 VERSION OF 2.5. IT IS ALSO UNDERSTOOD THAT THERE IS NO
 FEE ASSOCIATED WITH THE PATCH. THIS IS BASED ON
 INFORMATION GIVEN BY NUMEROUS DESIGNERS WHICH HAVE HAD
 TO UPDATE THE VERSION.
  
 2) NOTE: PLEASE SEE THAT METHOD *A* SUBMITTED FOR THE
 OFFICE SPACE IS NOT APPLICABLE.13-101. THE TENANT SPACE
 IS NOT A WHOLE BUILDING.
 PLEASE COORDINATE ALL ELECTRICAL ON PLANS AND OTHER
 COMPONENTS WITH THE SUBMITTED INPUT DATA REPORT.
 PLEASE SEE 13-101.1.6 FOR BUILDINGS WHICH ARE NOT
 COMPLETE. METHODS B OR C ARE THE ONLY CHOICE. NOT *A*.
 PIPING IS NOTED AS BEING INSULATED AS REQUIRED FOR HOT
 WATER HOWEVER THE ELECTRICAL PLANS AS WELL AS THE IDR
 DOES NOT INDICATE ANY INPUT FOR A HOT WATER HEATER?
  
 3) NOTE: PLEASE KNOW THAT HAND DRAWN ITEMS ARE NOT
 PERMITTED ON PLANS SIGNED, DATED AND SEALED. FS
 471.025. THIS IS NOT PERMITTED TO PLANS BY ARCHITECT OR
 ANY OTHER DESIGNER RESPONSIBLE FOR DRAWINGS.
 MANY OF THESE HAVE BEEN HIGH-LIGHTED ON PLANS.
  
 4) NOTE: THE SUBMITTED ENERGY CALCULATIONS MAKE NOTE TO
 LIGHTING CONTROL PANEL/CENTRAL CONTROLS HOWEVER THE
 PLANS DO NOT INDICATE THE LIGHTING CONTROLS AS
 REQUIRED. 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
  
 5) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE PANEL SCHEDULES. ONE EXAMPLE IS THE SIGN CIRCUIT
 WHICH PER 600.5 IS REQUIRED AT THE FRONT ENTRANCE FOR
 EACH SPACE AND IS REQUIRED TO BE ON DEDICATED
 CIRCUIT(S).
 PLEASE SEE ONE TENANT WHICH HAS CIRCUIT A-17 SHOWN AS
 GFI FOR SOME DEVICE.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETE OR ON PLANS FOR REVIEW A COMPLETE REVIEW OF
 SOME COULD NOT BE DONE AT THIS TIME. PLEASE BE SURE TO
 CALL TO GO OVER ANY QUESTIONS.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  