2008-12-01 11:24:43 | |
| ** FAILED REVIEW |
| |
| |
| 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE DONE |
| UNDER THE INCORRECT VERSION NOT ADOPTED BY THE FBC. |
| PLEASE SEE FBC 13-400.A.3 |
| PLEASE GO THE ENERGY GAUGE WEBSITE AS IT IS UNDERSTOOD |
| BY THIS OFFICE THERE IS A PATCH AVAIL FOR THE CORRECT |
| VERSION OF 2.5. IT IS ALSO UNDERSTOOD THAT THERE IS NO |
| FEE ASSOCIATED WITH THE PATCH. THIS IS BASED ON |
| INFORMATION GIVEN BY NUMEROUS DESIGNERS WHICH HAVE HAD |
| TO UPDATE THE VERSION. |
| |
| 2) NOTE: PLEASE SEE THAT METHOD *A* SUBMITTED FOR THE |
| OFFICE SPACE IS NOT APPLICABLE.13-101. THE TENANT SPACE |
| IS NOT A WHOLE BUILDING. |
| PLEASE COORDINATE ALL ELECTRICAL ON PLANS AND OTHER |
| COMPONENTS WITH THE SUBMITTED INPUT DATA REPORT. |
| PLEASE SEE 13-101.1.6 FOR BUILDINGS WHICH ARE NOT |
| COMPLETE. METHODS B OR C ARE THE ONLY CHOICE. NOT *A*. |
| PIPING IS NOTED AS BEING INSULATED AS REQUIRED FOR HOT |
| WATER HOWEVER THE ELECTRICAL PLANS AS WELL AS THE IDR |
| DOES NOT INDICATE ANY INPUT FOR A HOT WATER HEATER? |
| |
| 3) NOTE: PLEASE KNOW THAT HAND DRAWN ITEMS ARE NOT |
| PERMITTED ON PLANS SIGNED, DATED AND SEALED. FS |
| 471.025. THIS IS NOT PERMITTED TO PLANS BY ARCHITECT OR |
| ANY OTHER DESIGNER RESPONSIBLE FOR DRAWINGS. |
| MANY OF THESE HAVE BEEN HIGH-LIGHTED ON PLANS. |
| |
| 4) NOTE: THE SUBMITTED ENERGY CALCULATIONS MAKE NOTE TO |
| LIGHTING CONTROL PANEL/CENTRAL CONTROLS HOWEVER THE |
| PLANS DO NOT INDICATE THE LIGHTING CONTROLS AS |
| REQUIRED. 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4. |
| |
| 5) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH |
| THE PANEL SCHEDULES. ONE EXAMPLE IS THE SIGN CIRCUIT |
| WHICH PER 600.5 IS REQUIRED AT THE FRONT ENTRANCE FOR |
| EACH SPACE AND IS REQUIRED TO BE ON DEDICATED |
| CIRCUIT(S). |
| PLEASE SEE ONE TENANT WHICH HAS CIRCUIT A-17 SHOWN AS |
| GFI FOR SOME DEVICE. |
| |
| ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| COMPLETE OR ON PLANS FOR REVIEW A COMPLETE REVIEW OF |
| SOME COULD NOT BE DONE AT THIS TIME. PLEASE BE SURE TO |
| CALL TO GO OVER ANY QUESTIONS. |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |