2008-11-24 13:09:46BUILDING PLAN REVIEW
 PERMIT: 08070835
 ADD: 1256 PALM BEACH LAKES BLVD.
 CONT: MASTER CONSTRUCTION
 TEL: (561)248-5498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION. NOC FILED ON 7/22/08 WILL NEED TO BE FILED
 OVER 90 DAY OLD NO WORK.
  
 NOTE!!! THE PERMIT APPLICATION INDICATES THIS PERMIT IS
 TO FINISH WORK STATED UNDER THE EXPIRED PERMIT 05070295
 BUT THE PLANS INDICATE THE TOTAL SCOPE OF THE
 PROJECT.I'VE SPOKE WITH THE BUILDING OFFICIAL NEIL
 MELICK ABOUT THIS PROJECT. NEIL ADVISED EITHER THE
 CONTRACTOR TO PROVIDE A LETTER INDICATING THE SCOPING
 OF WORK TO BE COMPLETED UNDER THIS PERMIT. THE CHIEF
 INSPECTOR KEN CONRAD TO MAKE A JOBSITE VISIT TO CONFIRM
 THE SCOPING INDICATED WITHIN THE LETTER REFLECTS THE
 CORRECT AMOUNT OF WORK LEFT TO COMPLETEE THE PROJECT.
 WE WILL BE REVIEWING THE REMAINDER OF THE PROJECT UNDER
 THE 2004 FLORIDA BUILDING CODE, EXISTING BUILDING CODE.
 LETTER FROM THE CONTRACTOR FOR THE REMAINDER OF WORK TO
 BE COMPLETED UNDER THIS PERMIT IS ATTACHED TO PLAANS
 AND PERMIT APPLICATION.
 AS STATED IN THE CONTRACTORS LETTER SUB-PERMITS WILL
 ALSO NEED TO BE REAPPLIED FOR: ELECTRIC,PLUMBING,
 MECHANICAL, FIRE SPRINKLER, ROOFING, DUMPSTER ENCLOSURE
 AND SIGNAGE.
  
 2) 2ND REQUEST, THE DESIGNER WILL NEED TO UPDATE THE
 PLANS TO READ THE DESIGN NOT TO THE CURRENT CODE BUT TO
 THE 2004 FBC EXISTING BUILDING CODE 301.5 THE DESIGN
 PROFESSIONAL SHALL ELECT TO WHAT LEVEL ALTERATION THEY
 ARE DESIGNING TOO. LEVEL 1, LEVEL 2 OR LEVEL3.
  
 3) 2ND REQUEST, PLANS SUBMITTED DO NOT HAVE ANY ENERGY
 CALCULATIONS SUBMITTED, 2004 FBC EXISTING BUILDING CODE
 SECTION 611.1 MINIMUM REQUIREMENTS. ALTERATIONS SUBJECT
 TO THIS CHAPTER SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved