2008-08-12 15:30:54 | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE, CITY |
| OF WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), |
| FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA |
| STATUTES (F.S.). |
| |
| *** DENIED *** |
| ** WHEN THE MECHANICAL PLAN WAS REVIEW ON APRIL 14,2006 |
| A PROVISO WAS ATTACHED TO IT, THE REQUIREDMENTS OF THE |
| PROVISO WERE NOT MET SO THE PLAN MUST BE REVISED BEFOR |
| A NEW PERMIT CAN BE ISSUED. |
| |
| 1) RTU-6 IS NOT SHOWN ON PLAN MEP4 EQUIPMENT SCHEDULE, |
| PLEASE CORRECT PER 2001 FBC 104.3.1.1. |
| |
| 2) PLAN MEP-2 SHOW THE SIZE ON THE RETURN AIR DUCT |
| (FLEX) TO THE OFFICE (SEE YELLOW HIGH LIGHT ON |
| MECHANICAL PLAN). PER 2004 FBC/M 601.4. |
| |
| 3) CORRECTED. |
| |
| 4) PLEASE SHOW ON PLANS, COMPLIANCE WITH 2001 FBC/M |
| 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| |
| ** ADDITIONAL CORRECTIONS TO BE MADE TO PLAN MEP3. |
| |
| 5) RTU-6 SHOW THE SUPPLY DUCT (FLEX) AND SIZE, GOING TO |
| THE SUPPLY AIR GRILL IN THE OFFICE WITH NO DUCT (SEE |
| YELLOW HIGH LIGHT ON MECHANICAL PLAN). |
| |
| 6) RTU-6 PLAN SHOWS FLEX GOING FROM THE RETURN PLENUM |
| TO A MIXING BOX OR IS THAT A GRILL, PLEASE CLARIFY IF |
| IT'S A MIXING BOX OR A GRILL, SHOW THE SIZE OF THE FLEX |
| AND IF GRILL SHOW SIZE (SEE YELLOW HIGH LIGHT ON |
| MECHANICAL PLAN). |
| |
| 7) RTU-5 SHOW THE SIZE OF THE RETURN AIR GRILL (SEE |
| YELLOW HIGH LIGHT ON MECHANICAL PLAN). |
| |
| 8) RTU-5 PLAN MEP3 SHOWS AN ITEM NEAR THE WALL OF THE |
| RESTROOMS (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN) IS |
| THIS A SUPPLY AIR GRILL OR A WATER FOUNTAIN, PLEASE |
| CLARIFY. |
| |
| 9) PLEASE SUBMIT TWO SIGNED AND SEALED COPIES OF |
| PLANS. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729 |
| E-MAIL; [email protected] |