Plan Review Notes
Plan Review Notes For Permit 08070835
Permit Number 08070835
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-28 14:03:28***DENIED***
  
 1) SOME SHEETS ARE DIFFICULT TO READ. FBC 106.1.1
 REQUIRES CONSTRUCTION DOCUMENTS TO BE OF SUFFICIENT
 CLARITY TO REVIEW FOR CODE COMPLIANCE AND CONFORMANCE
 WITH RELEVANT LAWS, ORDINANCES RULES AND REGULATIONS.
  
 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 5) FIRE SPRINKLER SYSTEMS ARE REQUIRED FOR MERCANTILE
 OCCUPANCIES EXCEEDING 12,000 SQ'. NFPA 101, SEC.
 36.3.5.1 (2). PROVIDE FIRE SPRINKLER LAYOUT AS REQUIRED
 BY FBC. ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED PRIOR TO SYSTEM INSTALLATION.
  
 6) ADDRESS SHALL BE MINIMUM OF 6" IN HEIGHT, 1" WIDTH
 AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL
 BUILDINGS.
  
 7) PROVIDE LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756