Plan Review Notes For Permit 08070824 |
Permit Number |
08070824 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-30 17:00:07 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- PROVIDEINSTALLATION SCHEDULE AS REQUIRED BY CITY | | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT | | PROTECTION.SEE ATTACHED SAMPLE OR PROVIDE ANY OTHER | | FORMAT THAT PROVIDESALL THE REQUIRED INFORMATION. | | FILL IN ALL THE INFORMATION AS REQUIRED TO AVOID | | UNNECESSARY DELAYS. | | | | 2- CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING | | CONDITIONS (EG: WALL MOUNT, BUILT OUT, ETC) AND | | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED ACCORDING | | TO THEOPENING DESIGN PRESSURES,EDGE DISTANCE, PANEL | | SPAN, CONNECTION TYPE AND STRUCTURE TO BE ATTACHED TO | | (CONCRETE, CONCRETE BLOCK OR WOOD). SEE ANCHOR | | SCHEDULES ON SHUTTERS DRAWINGS. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 108.3 CITY AMENDMENTSTO FBC 2004. UPGRADE | | VALUATION AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|