2008-07-29 16:57:25 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- INSTALLATION SCHEDULE SUBMITTED SHOWS EDGE DISTANCE |
| TO BE 3". NEED TO REVISE ANCHOR SPACING AS REQUIRED BY |
| EDGE DISTANCE VERSUS SPACING FOR ANCHORS ON SHEET14 |
| OF 28.ANCHOR SPACING IS BASED ON EDGE DISTANCE OF 3 |
| 1/2". OTHERWISE NEED TO REDUCE THE ANCHOR SPACINGBY |
| MULTIPLYING0.83 SINCE EDGE DISTANCE SHOWN ON |
| INSTALLATION SCHEDULE IS 3". |
| |
| 2-PRODUCT APPROVAL SUBMITTED FL7288-R1WITH DRAWING |
| 06-174 WAS REVISED BY FL7288-R2 WITH DRAWING 07-184. |
| NEED TO PROVIDE CURRENT FLORIDA PRODUCT APPROVAL |
| FL7288-R2 AND CORRESPONDING DRAWING 07-184. |
| |
| 3- CLARIFY SHUTTER SPAN SHOWN ON COLUMN 5 OF |
| INSTALLATION SCHEDULE.EG: IFOPENING #1 IS 64" HIGH |
| HOW COME SHUTTER SPAN IS ONLY 43".THIS COMMENT |
| APPLIES TO ALL OPENINGS.PANEL SPAN DOESN'T REFLECT |
| SIZE OF OPENING. REVISE AS REQUIRED. |
| |
| 4- REVISE ANCHOR SPACING.INSTALLATION SCHEDULE CALLS |
| FOR2 1/4" TAPCONS, BUT ANCHOR TYPE HIGHLIGHTED ON |
| SHEET13 OF 26IS FOR ALL POINTS SOLID-SET ANCHOR. |
| AND ANCHOR TYPE HIGHLIGHTED ON SHEET 15 OF 26IS FOR |
| WEDGE-BOLT.REVISE AS REQUIRED TO MATCH ANCHOR SPACING |
| FOR TAPCONS AS SHOWN ON INSTALLATION SCHEDULE. (NOTE: |
| KEEP THIS IN CONSIDERATION WHEN USING REVISED DRAWING |
| 07-184. SEE ITEM #2 ABOVE). |
| |
| 5- REVISE TAPCON SIZE TO REFLECT MINIMUM EMBEDMENT |
| REQUIRED FOR CONCRETE AND CONCRETE BLOCKSUBSTRATE. |
| SEE SHEET 14 OF 26 FOR MINIMUM EMBEDMENT REQUIRED AND |
| REVISE AS REQUIRED. |
| |
| 6- INFORMATION SHOWN ON THE SUBSTRATE COLUMN OF |
| INSTALLATION SCHEDULE IS NOT CLEAR.IS IT CONCRETE, |
| CONCRETE BLOCK OR WOOD? |
| |
| 7-PERMIT APPLICATION AND KEY PLAN SHOW 8OPENINGS, |
| WHILE INSTALLATION SCHEDULE ONLY SHOW 7 OPENINGS. |
| PROVIDE COMPLETE INFORMATION. |
| |
| 8-PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| BY SEC. 713.13 FLORIDA STATUTE. |
| |
| 9- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE, OWES |
| $32.81 FOR UPDATED VALUATION. |
| |