Plan Review Notes
Plan Review Notes For Permit 08070718
Permit Number 08070718
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-10 09:49:31 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 REPEAT COMMENTS FROM THE PREVIOUS REVIEW***INDICATES
 FURTHER EXPLANATION OF PREVIOUS COMMENT
  
 1} THE MANUFACTURERS SPECIFICATION FOR THE GENERATOR
 ARE PARTIALLY INDISCERNIBLE, PLEASE SUBMIT READABLE
 COPIES***THE SAME SPEC'S RESUBMITTED.
  
 2} THE RESPONSE TO THE PREVIOUS REVIEW COMMENT #3WAS
 THAT THE OCP IS IN THE GENERATOR CONTROL PANEL, THERE
 IS NO INDICATION OF THAT IN THE SPECIFICATIONS
 SUBMITTED.***CORRECT, THE 3000AMP OCP IS NOTED ON SHEET
 E2.
  
 3} INDICATE IF ANY REQUIRED EMERGENCY LIGHTING OR OTHER
 SYSTMS WILL OPERATE FROM THIS GENERATOR POWER.PROVIDE A
 RISER DIAGRAM INDICATING WHICH PANELS WILL BE FED FROM
 THIS GENERATOR. THE SUBMITTED PLAN SHOWS THE GENERATOR
 FEEDING "MDP."*** NO RESPONSE GIVEN TO THIS COMMENT.
  
 NEW COMMENT GENERATED AS THE DISCONNECTING MEANS IN THE
 NEXGEAR NOW IS THE FIRST MEANS OF DISCONNECT.
  
 4} SHEET E2, NOTE #9 DOES NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR PER 250.130(A) FOR GROUNDED SYSTEMS
 THE CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT
 GROUNDING CONDUCTOR TO THE GROUNDED SERVICE CONDUCTOR
 AND THE GROUNDING ELECTRODE CONDUCTOR. THEREFORE AS THE
 EQUIPMENT GROUND ORIGINATES FROM THE FIRST MEANS OF
 DISCONNECT IT MUST BE RUN WITH THE FEEDERS FROM
 "NEXGEAR" SWITCHGEAR. "250.32(2)(B) GROUNDED CONDUCTOR
 WHERE (1) AN EQUIPMENT GROUNDING CONDUCTOR IS NOT RUN
 WITH THE SUPPLY TO THE BUILDING OR STRUCTURE, (2) THERE
 ARE NO CONTINUOUS METALLIC PATHS BONDED TO THE
 GROUNDING SYSTEM IN EACH BUILDING OR STRUCTURE
 INVOLVED,".THE CONTINUOUS PATH IS THE CONTROL
 WIRING.SEE SHEET E6 AND E4.***THE NEXGEAR IS THE FIRST
 MEANS OF DISCONNECT SEE 250.24(A)(5). NOT ALL CONTROL
 WIRING WILL GO TO NORMALLY OPEN CONTACTS. SEE NOTES ON
 SHEET *6.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718