Plan Review Notes
Plan Review Notes For Permit 08070718
Permit Number 08070718
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-01 16:10:25 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE MANUFACTURERS SPECIFICATION FOR THE GENERATOR
 ARE PARTIALLY INDISCERNIBLE, PLEASE SUBMIT READABLE
 COPIES.
  
 2} THE RESPONSE TO THE PREVIOUS REVIEW COMMENT #3WAS
 THAT THE OCP IS IN THE GENERATOR CONTROL PANEL, THERE
 IS NO INDICATION OF THAT IN THE SPECIFICATIONS
 SUBMITTED.
  
 3} INDICATE IF ANY REQUIRED EMERGENCY LIGHTING OR OTHER
 SYSTMS WILL OPERATE FROM THIS GENERATOR POWER.PROVIDE A
 RISER DIAGRAM INDICATING WHICH PANELS WILL BE FED FROM
 THIS GENERATOR. THE SUBMITTED PLAN SHOWS THE GENERATOR
 FEEDING "MDP."
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718