Plan Review Notes For Permit 08070715 |
Permit Number |
08070715 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-12 09:33:18 | PLUMBING PLAN REVIEW: | | DENIED: | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #8 EW-1: | | THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1 | | DOES NOT COMPLY WITH THE FBC-2004 PLUMBING . PLEASE | | KNOW THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE | | INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED | | LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004 | | PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING | | VALVES. | | | | ********IMPORTANT INFORMATION******** | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | PHONE= (561) 805-6730 | | FAX= (561) 805-6731 | | E-MAIL= [email protected] |
|