2008-08-12 09:33:18PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #8 EW-1:
 THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1
 DOES NOT COMPLY WITH THE FBC-2004 PLUMBING . PLEASE
 KNOW THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE
 INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED
 LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004
 PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING
 VALVES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  