Plan Review Notes
Plan Review Notes For Permit 08070715
Permit Number 08070715
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-12 10:59:33*****DENIED*****
  
  
 1.STRUCTURES UNDERGOIG CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO GENERAL DEMOLITION NOTES (SHEET A0.2)
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.AMEND
 GENERAL DEMOLITION NOTE #4 (SHEET A0.2)
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.INDICATE/SHOW HOW THE SCOPE OF WORK WILL HAVE CAUSE
 FOR ANY FIRE ALARM DEVICES TO BE RELOCATED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722