Plan Review Notes For Permit 08070715 |
Permit Number |
08070715 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-08-12 10:59:33 | *****DENIED***** | | | | | | 1.STRUCTURES UNDERGOIG CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | COMMENT TO GENERAL DEMOLITION NOTES (SHEET A0.2) | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.AMEND | | GENERAL DEMOLITION NOTE #4 (SHEET A0.2) | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 4.INDICATE/SHOW HOW THE SCOPE OF WORK WILL HAVE CAUSE | | FOR ANY FIRE ALARM DEVICES TO BE RELOCATED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|